DeviceNet
9
Technical data
9-2
L
BA2175 EN 2.0
9.3
General data and application conditions
For
Values
Order name
33.2175IB
Communication media
DIN ISO 11898
Baud rate [kBit/s]
125, 250, 500
Ambient temperature
during operation:
-20
°
C
to
60
°
C
during transport:
-25
°
C
to
70
°
C
during storage
-25
°
C
to
60
°
C
Permissible humidity
Class 3K3 to EN 50178 (without condensation, average relative humidity 85%)
24-V-DC-
Voltage supply
•
external supply only: 820X
•
internal or external supply: 93XX / 9300 servo PLC / 821X / 822X / 8200 vector (see chapter 4.3.2)
9.4
Rated data
For
Values
Voltage supply
24 V DC
ñ
10 %; max. 100 mA
Communication medium ISO 11898
Rated insulation voltage
Type of insulation
•
PE
50VAC
Electrical isolation
•
External supply (term. 39/59)
-
No electrical isolation
•
Power stage
– 820X / 821X
270 V AC
Basic insulation
– 822X / 8200 vector
270 V AC
Double insulation
Ins lation oltages for
– 93XX
270 V AC
Double insulation
Insulation voltages for
bus systems
•
Control terminals:
bus systems
– 820X / 8200 vector
(with internal supply)
-
No electrical isolation
– 8200 vector
(with external supply)
100 V AC
Basic insulation
– 821X
50 V AC
Electrical isolation
– 822X
270 V AC
Basic insulation
– 93XX
270 V AC
Basic insulation
•
External bus systems
0 V AC
No electrical isolation
Pollution degree
VDE0110, part 2, pollution degree 2
9.5
Dimensions
75
62
36
18
DeviceNet
CANopen
Fig. 9-1
Dimensions: 2175 fieldbus module (all dimensions in mm)