CANopen
4
Installation
4-6
L
BA2175 EN 2.0
4.4.1
CAN bus wiring
2175DeN002
2175
V-
V+
CAN_L
CAN_H
SHLD
120
R
120
R
CAN
LOW
HIGH
Please observe our recommendations for signal cables:
Total length up to 300 m
Cable type
LIYCY 2 x 2 x 0.5 mm
2
(twisted in pairs with shield)
Cable resistance
≤
40
Ω
/km
Capacitance per unit length
≤
130 nF/km
Total length up to 1000 m
Cable type
CYPIMF 2 x 2 x 0.5 mm
2
(twisted in pairs with shield)
Cable resistance
≤
40
Ω
/km
Capacitance per unit length
≤
60 nF/km
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: [email protected]