If this unit has been used for heating or cooling of
buildings or structures under construction, the following
conditions must be met or the warranty will be void:

  

A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or
cooling is not allowed.

  

A pre-filter must be installed at the entry to the return
air duct.

  

The return air duct must be provided and sealed to
the unit.

  

Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.

  

Air filters must be replaced and pre-filters must be
removed upon construction completion.

  

The input rate and temperature rise must be set per
the unit rating plate.

  

The heat exchanger, components, duct system, air
filters and evaporator coil must be thoroughly
cleaned following final construction clean-up.

  

The unit operating conditions (including airflow,
cooling operation, ignition, input rate, temperature
rise and venting) must be verified according to these
installation instructions.

Unit Support 

In downflow discharge installations, install the unit on a
non-combustible surface only. Unit may be installed on
combustible surfaces when used in horizontal discharge
applications or in downflow discharge applications when
installed on an Z1CURB roof mounting frame.

NOTE - Securely fasten roof frame to roof per local codes.

A-Downflow Discharge Application

Roof Mounting with Z1CURB

1- The Z1CURB roof mounting frame must be installed,

flashed and sealed in accordance with the
instructions provided with the frame.

2- The Z1CURB roof mounting frame should be square

and level to 1/16” per linear foot (5mm per linear
meter) in any direction.

3- Duct must be attached to the roof mounting frame

and not to the unit; supply and return plenums must
be installed before setting the unit.

Installer's Roof Mounting Frame

Many types of roof frames can be used to install the unit
depending upon different roof structures. Items to keep
in mind when using the building frame or supports are:

1- The base is fully enclosed and insulated, so an

enclosed frame is not required.

2- The frames or supports must be constructed with

non-combustible materials and should be square and
level to 1/16” per linear foot (5mm per linear meter)
in any direction.

3- Frame or supports must be high enough to prevent

any form of moisture from entering unit.
Recommended minimum frame height is 14”
(356mm).

4- Duct must be attached to the roof mounting frame

and not to the unit. Supply and return plenums must
be installed before setting the unit.

5- Units require support along all four sides of unit base.

Supports must be constructed of steel or suitably
treated wood materials.

NOTE-When installing a unit on a combustible surface for
downflow discharge applications, an Z1CURB roof
mounting frame is required.

B-Horizontal Discharge Applications

1- Specified installation clearances must be maintained

when installing units. Refer to figure 1.

2- Top of support slab should be approximately 4”

(102mm) above the finished grade and located so no
run-off water from higher ground can collect around
the unit.

3- Units require support along all four sides of unit base.

Supports must be constructed of steel or suitably
treated wood materials.

Duct Connection 

All exterior ducts, joints and openings in roof or building
walls must be insulated and weather-proofed with
flashing and sealing compounds in accordance with
applicable codes. Any duct passing through an
unconditioned space must be insulated.

CAUTION

In downflow applications, do not drill or punch
holes in base of unit. Leaking in roof may occur if
unit base is punctured.

Summary of Contents for ZHA092

Page 1: ...TALLATION INSTRUCTIONS ZHA092 ZHA102 ZHA120 7 5 Ton 8 5 Ton 10 Ton HEAT PUMP PACKAGED UNITS 507257 01 7 2014 Electrical Connections Page 6 Unit Power Up Page 6 Blower Operation and Adjustments Page 7...

Page 2: ...WER 24V ACC 1 1 4 1 2 Hole Diameter Required in Unit Base Max Wire Use BOTTOM POWER ENTRY Holes required for Optional Bottom Power Entry Kit Threaded Conduit Fittings Provided in Kit A B C 1 2 39 991...

Page 3: ...filters will damage the unit IMPORTANT The Clean Air Act of 1990 bans the intentional vent ing of refrigerant CFC s and HCFC s as of July 1 1992 Approved methods of recovery recycling or reclaiming mu...

Page 4: ...and not to the unit supply and return plenums must be installed before setting the unit Installer s Roof Mounting Frame Many types of roof frames can be used to install the unit depending upon differ...

Page 5: ...BRACKETS AND BASE PROTECTION BOARD FIGURE 3 UNIT ALIGNMENT BRACKETS THREE 3 UNIT ALIGNMENT BRACKETS ROOF CURB NEW ROOF CURBS 89 3 8 IN LENGTH Remove all three brackets EXISTING ROOF CURBS 81 3 4 LONG...

Page 6: ...secure thermostat cable Use18 AWG wire for all applications using remotely installed electro mechanical and electronic thermostats 2 Install thermostat assembly in accordance with instructions provide...

Page 7: ...wers will operate continuously 2 With fan switch in AUTO position the blowers will cycle with demand Blowers and entire unit will be off when system switch is in OFF position C Blower Access The blowe...

Page 8: ...ns Open A Section 0 5 B Section 1 6 No minimum number of turns open when B belt is used on pulleys 6 O D or larger E Blower Belt Adjustment Maximum life and wear can be obtained from belts only if pro...

Page 9: ...5 8 Example Deflection distance of a 400mm span would be 6mm 3 Measure belt deflection force For a new 2 and 3hp belt the deflection force should be 5 0 7 0 lbs 35 48kPa For a new 5hp belt the deflec...

Page 10: ...0 49 650 0 70 719 0 87 786 0 98 852 1 09 915 1 20 972 1 32 1026 1 47 1076 1 65 2250 533 0 41 599 0 62 667 0 82 735 0 99 802 1 10 866 1 21 928 1 33 984 1 46 1037 1 63 1085 1 81 1132 2 01 1178 2 21 122...

Page 11: ...913 1 57 968 1 74 1020 1 93 1068 2 13 1116 2 34 1165 2 56 1215 2 78 1268 3 01 3000 620 0 95 678 1 11 741 1 25 806 1 40 870 1 58 930 1 75 985 1 94 1036 2 14 1084 2 36 1131 2 58 1180 2 80 1230 3 02 128...

Page 12: ...0 25 0 34 0 07 0 12 0 22 5750 0 27 0 25 0 31 0 45 0 07 0 12 0 25 6000 0 29 0 27 0 33 0 52 0 08 0 13 0 27 BLOWER DATA FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS Nominal hp Maximum hp Drive Kit Nu...

Page 13: ...tructions provided with thermostat 2 No Economizer Installed in Unit A first stage cooling demand Y1 will energize compressor 1 and both condenser fans An increased cooling demand Y2 will energize com...

Page 14: ...or ambient and a measured suction pressure of 130psig the target liquid temperature is 103 F For a measured liquid temperature of 106 F add charge in increments until measured liquid temperature agree...

Page 15: ...337 115 385 118 436 121 492 Circuit 1 110 253 118 297 126 346 128 398 136 450 135 505 113 260 122 302 130 351 137 404 144 458 143 515 119 240 124 281 128 322 131 368 135 419 138 473 Circuit 2 124 244...

Page 16: ...19 337 120 383 121 430 127 491 Circuit 1 124 265 132 309 137 355 141 405 145 459 145 515 129 268 138 312 146 363 153 415 159 472 160 530 116 260 119 298 123 340 126 385 131 437 136 405 125 266 128 306...

Page 17: ...161 474 161 531 114 265 115 302 119 345 122 390 125 443 130 496 Circuit 2 121 269 125 310 127 354 131 401 134 448 137 498 132 279 140 319 145 365 148 414 152 469 155 524 137 284 147 329 155 379 163 4...

Page 18: ...g jumper is in the TEST position at power up the defrost control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the...

Page 19: ...actory with temporary filters Replace filters before building is occupied Damage to unit could result if filters are not re placed with approved filters Refer to appropriate codes Approved filters sho...

Page 20: ...with water following cleaning Note Remove all screws and gaskets prior to cleaning procedure and replace upon completion J Supply Air Blower Wheel Annually inspect supply air blower wheel for accumul...