background image

Page 14

IMPORTANT - Charge unit in standard cooling mode.

1- Make sure outdoor coil is clean. Attach gauge

manifolds and operate unit at full CFM in cooling mode
with economizer disabled until system stabilizes
(approximately five minutes). Make sure all outdoor air
dampers are closed.

2- Check each system separately with all stages

operating. Compare the normal operating pressures
(see tables 3 - 5) to the pressures obtained from the
gauges. Check unit components if there are
significant differences.

3- Measure the outdoor ambient temperature and the

suction pressure. Refer to the appropriate circuit
charging curve to determine a target liquid
temperature.

Note - Pressures are listed for sea level applications.

4- Use the same thermometer to accurately measure the

liquid temperature (in the outdoor section).

If measured liquid temperature is higher than

the target liquid temperature, add refrigerant to
the system.

If measured liquid temperature is lower than

the target liquid temperature, recover some
refrigerant from the system.

5- Add or remove charge in increments. Allow the

system to stabilize each time refrigerant is added or
removed.

6- Continue the process until measured liquid

temperature agrees with the target liquid
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.

7- Example ZH 092S Circuit 1: At 95°F outdoor ambient

and a measured suction pressure of 130psig, the
target liquid temperature is 103°F. For a measured
liquid temperature of 106°F, add charge in
increments until measured liquid temperature agrees
with the target liquid temperature.

C-Compressor Controls

1- High Pressure Switches (S4, S7)

Compressor circuits are protected by a high pressure
switch which cuts out at 640 psig + 10 psig (4413 kPa
+ 70 kPa).

2- High Temperature Limit Switches (S5, S8)

Switches de-energize compressors when the
temperature on top of the compressor exceeds
248

F (120

C). Switches reset when temperature

cools to 169

F (76

C).

3- Defrost Switches (S6, S9)

Defrost switches close to initiate defrost when liquid
line temperature falls to 35

F (1.7

C). The defrost

switch is located on the liquid line between the
outdoor expansion valve and the distributor

4- Defrost Termination Switch (S104)

Defrost pressure switch opens to terminate defrost
when vapor (discharge pressure during cooling and
defrost) pressure reaches 450 psig (3103 kPa).

5- Defrost Controls (CMC1)

Defrost is liquid line temperature initiated and
operates for 14 minutes unless terminated by vapor
line pressure drop.

When the liquid line temperature drops below 35°F,
the defrost switch closes and signals the 

defrost

control

 that a defrost cycle is needed. If the defrost

switch is still closed after 60 minutes (default), a
defrost cycle begins and operates for 14 minutes.
The defrost pressure switch can terminate the defrost
cycle before the 14 minutes elapses if vapor pressure
reaches 450 + 10 psi

.

Electric heat is energized during defrost to maintain
discharge air temperature.

Summary of Contents for ZHA092

Page 1: ...TALLATION INSTRUCTIONS ZHA092 ZHA102 ZHA120 7 5 Ton 8 5 Ton 10 Ton HEAT PUMP PACKAGED UNITS 507257 01 7 2014 Electrical Connections Page 6 Unit Power Up Page 6 Blower Operation and Adjustments Page 7...

Page 2: ...WER 24V ACC 1 1 4 1 2 Hole Diameter Required in Unit Base Max Wire Use BOTTOM POWER ENTRY Holes required for Optional Bottom Power Entry Kit Threaded Conduit Fittings Provided in Kit A B C 1 2 39 991...

Page 3: ...filters will damage the unit IMPORTANT The Clean Air Act of 1990 bans the intentional vent ing of refrigerant CFC s and HCFC s as of July 1 1992 Approved methods of recovery recycling or reclaiming mu...

Page 4: ...and not to the unit supply and return plenums must be installed before setting the unit Installer s Roof Mounting Frame Many types of roof frames can be used to install the unit depending upon differ...

Page 5: ...BRACKETS AND BASE PROTECTION BOARD FIGURE 3 UNIT ALIGNMENT BRACKETS THREE 3 UNIT ALIGNMENT BRACKETS ROOF CURB NEW ROOF CURBS 89 3 8 IN LENGTH Remove all three brackets EXISTING ROOF CURBS 81 3 4 LONG...

Page 6: ...secure thermostat cable Use18 AWG wire for all applications using remotely installed electro mechanical and electronic thermostats 2 Install thermostat assembly in accordance with instructions provide...

Page 7: ...wers will operate continuously 2 With fan switch in AUTO position the blowers will cycle with demand Blowers and entire unit will be off when system switch is in OFF position C Blower Access The blowe...

Page 8: ...ns Open A Section 0 5 B Section 1 6 No minimum number of turns open when B belt is used on pulleys 6 O D or larger E Blower Belt Adjustment Maximum life and wear can be obtained from belts only if pro...

Page 9: ...5 8 Example Deflection distance of a 400mm span would be 6mm 3 Measure belt deflection force For a new 2 and 3hp belt the deflection force should be 5 0 7 0 lbs 35 48kPa For a new 5hp belt the deflec...

Page 10: ...0 49 650 0 70 719 0 87 786 0 98 852 1 09 915 1 20 972 1 32 1026 1 47 1076 1 65 2250 533 0 41 599 0 62 667 0 82 735 0 99 802 1 10 866 1 21 928 1 33 984 1 46 1037 1 63 1085 1 81 1132 2 01 1178 2 21 122...

Page 11: ...913 1 57 968 1 74 1020 1 93 1068 2 13 1116 2 34 1165 2 56 1215 2 78 1268 3 01 3000 620 0 95 678 1 11 741 1 25 806 1 40 870 1 58 930 1 75 985 1 94 1036 2 14 1084 2 36 1131 2 58 1180 2 80 1230 3 02 128...

Page 12: ...0 25 0 34 0 07 0 12 0 22 5750 0 27 0 25 0 31 0 45 0 07 0 12 0 25 6000 0 29 0 27 0 33 0 52 0 08 0 13 0 27 BLOWER DATA FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS Nominal hp Maximum hp Drive Kit Nu...

Page 13: ...tructions provided with thermostat 2 No Economizer Installed in Unit A first stage cooling demand Y1 will energize compressor 1 and both condenser fans An increased cooling demand Y2 will energize com...

Page 14: ...or ambient and a measured suction pressure of 130psig the target liquid temperature is 103 F For a measured liquid temperature of 106 F add charge in increments until measured liquid temperature agree...

Page 15: ...337 115 385 118 436 121 492 Circuit 1 110 253 118 297 126 346 128 398 136 450 135 505 113 260 122 302 130 351 137 404 144 458 143 515 119 240 124 281 128 322 131 368 135 419 138 473 Circuit 2 124 244...

Page 16: ...19 337 120 383 121 430 127 491 Circuit 1 124 265 132 309 137 355 141 405 145 459 145 515 129 268 138 312 146 363 153 415 159 472 160 530 116 260 119 298 123 340 126 385 131 437 136 405 125 266 128 306...

Page 17: ...161 474 161 531 114 265 115 302 119 345 122 390 125 443 130 496 Circuit 2 121 269 125 310 127 354 131 401 134 448 137 498 132 279 140 319 145 365 148 414 152 469 155 524 137 284 147 329 155 379 163 4...

Page 18: ...g jumper is in the TEST position at power up the defrost control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the...

Page 19: ...actory with temporary filters Replace filters before building is occupied Damage to unit could result if filters are not re placed with approved filters Refer to appropriate codes Approved filters sho...

Page 20: ...with water following cleaning Note Remove all screws and gaskets prior to cleaning procedure and replace upon completion J Supply Air Blower Wheel Annually inspect supply air blower wheel for accumul...

Reviews: