background image

Page 22

C−Burners

  1− Periodically  examine  burner  flames  for  proper

appearance 

during 

the 

heating 

season. 

Use

inspection  port  in  the  front  of  the  burner  compartment
access  panel.

  2− Before  each  heating  season  examine  the  burners  for

any  deposits  or  blockage  which  may  have  occurred.

  3− Clean  burners  as  follows:

a−Turn  off  both  electrical  power  and  gas  supply  to
unit.

b−Remove  access  panel  to  burner  compartment.

c−Remove  burner  mounting  screws  and  lift  burners
from  orifice.

d−Clean  as  necessary  and  replace  burners  and  secure
with  mounting  screws.  Make  sure  that  burner  heads
line  up  correctly.  Spark  gaps  on  ignitor  and  flame
sensing  electrode  must  be  properly  set.  Refer  to
Heating  Adjustment  section.  Replace  access  panel.

 

WARNING

Danger  of  explosion.  Can  cause  injury  or
death.  Do  not  overtighten  main  burner
mounting  screws.  Snug  tighten  only.

e−  Restore  electrical  power  and  gas  supply.  Follow
lighting  instructions  located  on  inside  panel.  Use
inspection  port  in  access  panel  to  check  flame.

D−Combustion  Air  Inducer

A  combustion  air  blower  motor  proving  switch,  S18,

checks  combustion  air  inducer  operation  before  allowing

power  to  the  gas  controller.  Gas  controller  will  not  operate

if  inducer  is  obstructed.

Under  normal  operating  conditions,  the  combustion  air

inducer  wheel  should  be  checked  and  cleaned  prior  to  the

heating  season.  However,  it  should  be  examined

periodically  during  the  heating  season  to  establish  an

ideal 

cleaning 

schedule. 

With 

power 

supply

disconnected,  the  condition  of  the  inducer  wheel  can  be

determined  by  looking  through  the  vent  opening.

Cleaning  Combustion  Air  Inducer  and  Vent  Cap

  1− Shut  off  power  supply  and  gas  to  unit.

  2− Remove  the  heat  access  panel.  Disconnect  motor

wires  &  three  motor  mounting  screws.

  3− Clean  inducer  wheel  with  a  small  brush  and  wipe  off

any  dust  from  housing.  See  figure  23.  Clean

accumulated  dust  from  front  of  flue  box  cover.  Inspect

flue  passageway  and  flue  box  when  removing  the

combustion  air  inducer.  If  cleaning  is  necessary  use

wire  brush.

CLEAN  INDUCER  WHEEL  WITH  BRUSH

FIGURE  23

  4− Replace  combustion  air  inducer  motor  by  reversing

this 

procedure. 

It 

is 

recommended 

that 

the

combustion  air  inducer  gasket  be  replaced  during

reassembly.

  5− Clean  combustion  air  supply  (hood  located  on  heat

access  panel)  using  a  small  brush.

E−Evaporator  Coil

 

WARNING

Electric  shock  hazard.  Can  cause
injury  or  death.  Before  attempting  to
perform  any  service  or  maintenance,
turn  the  electrical  power  to  unit  OFF  at
disconnect  switch(es).  Unit  may  have
multiple  power  supplies.

Inspect  and  clean  coil  at  beginning  of  each  cooling  and

heating 

season. 

Clean 

using 

mild 

detergent 

or

commercial  coil  cleanser.  Flush  coil  and  condensate

drain  with  water  taking  care  not  to  get  insulation,  filters,

return  air  ducts  wet.

Summary of Contents for Humiditrol L Series

Page 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Page 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Page 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Page 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Page 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Page 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Page 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Page 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Page 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Page 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Page 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Page 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Page 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Page 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Page 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Page 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Page 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Page 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Page 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Page 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Page 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Page 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Page 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Page 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Reviews: