background image

Page 9

Blower  Operation  and  Adjustments

NOTE  −  These  units  must  not  be  used  as  a  4construction
heater"  at  any  time  during  any  phase  of  construction.
Very  low  return  air  temperatures,  harmful  vapors,  and
misplacement  of  the  filters  will  damage  the  unit  and  its
efficiency.  Additionally,  a  unit  which  will  be  subject  to  cold
temperatures  when  not  in  operation  must  have  a  vapor
barrier  installed  to  seal  the  duct  connections.  Failure  to
protect  the  unit  from  moisture  laden  air  or  harmful  vapors
(generated 

from 

the 

construction 

process 

and

temporary  combustion  heating  equipment)  will  cause
corrosive  condensation  within  the  unit.  Failure  to
properly  protect  the  unit  in  this  situation  will  cause
electrical  and  electronic  component  failure  and  could
affect  the  unit  warranty  status.

A−Blower  Operation

  1− Blower  operation  is  manually  set  at  the  thermostat

subbase  fan  switch.  With  fan  switch  in  ON  position,
blowers  will  operate  continuously.

  2− With  fan  switch  in  AUTO  position,  the  blower  will  cycle

with  demand.  Blower  and  entire  unit  will  be  off  when
system  switch  is  in  OFF  position.

B−Determining  Unit  CFM

  1− The  following  measurements  must  be  made  with  a

dry  indoor  coil.  Run  blower  without  a  cooling  demand.
Air  filters  must  be  in  place  when  measurements  are
taken.

  2− Measure  static  pressure  external  to  unit  (from  supply

to  return).

  3− Measure  the  indoor  blower  wheel  RPM.

  4− Refer  to  unit  nameplate  to  determine  the  blower

motor  horse  power.

  5− Referring  to  table  2  or  3,  use  the  static  pressure  and

RPM  readings  to  determine  unit  CFM.

  6− The  CFM  can  be  adjusted  at  the  motor  pulley  (see

section  C−Blower  Belt  Adjustment).

C−Blower  Belt  Adjustment

Maximum  life  and  wear  can  be  obtained  from  belts  only  if
proper  pulley  alignment  and  belt  tension  are  maintained.

Important−Tension  new  belt  after  a  24−48  hour  period  of
operation.  This  will  allow  belts  to  stretch  and  seat
grooves.  To  increase  belt  tension,  loosen  2  locking  bolts
and  pull  mounting  plate.  Tighten  motor  mounting  plate  in
vertical  position.  See  figure  13.

FIGURE  13

BLOWER  SPEED  ADJUSTMENT

BLOWER

WHEEL

MOTOR  &  PULLEY

TO  INCREASE  CFM

LOOSEN  ALLEN  SCREW  &

TURN  PULLEY  CLOCKWISE

TO  DECREASE  CFM

TURN  PULLEY

COUNTERCLOCKWISE

TO  INCREASE  BELT  TENSION

1  −  Loosen  2  locking  bolts.
2  −  Pull  motor  mounting  plate.
3  −  Tighten  motor  mounting  plate  so  plate  is  vertical.

MOTOR  MOUNTING  PLATE

LOCKING  BOLTS

BELT

SET

SCREW

KEY

D−Check  Belt  Tension

Overtensioning  belts  shortens  belt  and  bearing  life.
Check  belt  tension  as  follows:

  1− Measure  span  length  X.  See  figure  14.

  2− Apply  perpendicular  force  to  center  of  span  (X)  with

enough  pressure  to  deflect  belt  1/64"  for  every  inch  of
span  length  or  1.5mm  per  100mm  of  span  length.

Example:  Deflection  distance  of  a  40"  span  would  be
40/64"  or  5/8".

Example:  Deflection  distance  of  a  400mm  span
would  be  6mm.

  3− Measure  belt  deflection  force.  For  a  used  belt,  the

deflection  force  should  be  5  lbs.  (35kPa)  .  A  new  belt
deflection  force  should  be  7  lbs.  (48kPa).

force 

below 

these 

values 

indicates 

an

undertensioned  belt.  A  force  above  these  values
indicates  an  overtensioned  belt.

MEASURE  BELT  TENSION

FIGURE  14

DEFLECTION  1/64"  PER  INCH  OF  SPAN

OR  1.5mm  PER  100mm  OF  SPAN

FORCE

Summary of Contents for Humiditrol L Series

Page 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Page 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Page 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Page 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Page 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Page 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Page 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Page 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Page 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Page 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Page 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Page 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Page 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Page 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Page 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Page 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Page 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Page 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Page 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Page 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Page 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Page 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Page 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Page 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Reviews: