background image

Page 5

Condensate  Drains

Make  drain  connection  to  the  3/4"  N.P.T.  drain  nipple
provided  on  unit.  A  trap  must  be  installed  between  drain
connection  and  an  open  vent  for  proper  condensate
removal.  See  figure  5.  It  is  sometimes  acceptable  to  drain
condensate  onto  the  roof  or  grade;  however,  a  tee  should
be  fitted  to  the  trap  to  direct  condensate  downward.  The
condensate  line  must  be  vented.  Check  local  codes
concerning  condensate  disposal.  Refer  to  figures  1  and  2
for  condensate  drain  location.

FIGURE  5

Á

Á

Á

Á

Á

Á

Á

Á

Á

Á

Á

Á

Á

Á

Á

UNIT

Minimum  Pitch
1"  (25mm)  per
  10’  (3m)  of  line

MOUNTING  FRAME

OPEN  VENT

CONDENSATE  DRAIN  CONNECTION

CAULK  AROUND

CONDENSATE

COUPLING

Connect  Gas  Piping

Before  connecting  piping,  check  with  gas  company  or
authorities 

having 

jurisdiction 

for 

local 

code

requirements.  When  installing  gas  supply  piping,  length
of  run  from  gas  meter  must  be  considered  in  determining
pipe  size  for  0.5"  w.c.  maximum  pressure  drop.  Do  not
use  supply  pipe  smaller  than  unit  gas  connection.  For
natural  gas  units,  operating  pressure  at  the  unit  gas
connection  must  be  a  minimum  of  5.5"  w.c.  and  a
maximum  of  10.5"  w.c.  For  propane  gas  units,  operating
pressure  at  the  unit  gas  connection  must  be  a  minimum
of  11"  w.c.  and  a  maximum  of  13.0"  w.c.

When  making  piping  connections,  a  drip  leg  should  be
installed  on  vertical  pipe  runs  to  serve  as  a  trap  for
sediment  or  condensate.  A  1/8"  N.P.T.  plugged  tap  in
field  piping  accessible  for  test  gauge  connection  must
be  provided  upstream  of  gas  supply  connection  to  the
unit.  Install  a  ground  joint  union  between  the  gas
control  manifold  and  the  main  manual  shut−off  valve.
See  figure  6.

Compounds  used  on  threaded  joints  of  gas  piping  shall
be  resistant  to  the  action  of  liquified  petroleum  gases.

GAS  PIPING

SUPPORT

UNIT

FIGURE  6

FIELD  PROVIDED

1/8"  PRESSURE  TAP

GROUND

JOINT  UNION

MANUAL  MAIN

SHUT−OFF  VALVE

(REFER  TO

LOCAL

CODES)

DRIP  LEG

UNIT

SUPPORT

GAS  PIPE  CONNECTION

Pressure  Test  Gas  Piping

When  pressure  testing  gas  lines,  the  gas  valve  must  be
disconnected  and  isolated.  Gas  valves  can  be  damaged  if
subjected  to  more  than  0.5  psig  (14"  w.c.).  See  figure  7.

If  the  test  pressure  is  equal  to  or  less  than  0.5  psig  (14"
w.c.),  use  the  main  manual  shut−off  valve  before  pressure
testing  to  isolate  the  unit  from  the  gas  supply  system.  If
necessary, 

adjust 

main 

gas 

supply 

pressure 

in

accordance 

with 

HConnect 

Gas 

Pipe" 

section.

GAS  VALVE

CAP

MANUAL  MAIN

SHUT−OFF  VALVE

FIGURE  7

PRESSURE  TEST  GAS  VALVE

NOTE−Codes  may  require  that  manual  main  shut−off  valve
and  union  (furnished  by  installer)  be  installed  in  gas  line
external  to  unit.  Union  must  be  of  the  ground  joint  type.

After  all  connections  have  been  made,  check  all  piping
connections  for  gas  leaks.  Also  check  existing  gas
connections  up  to  the  gas  valve;  loosening  may  occur
during  installation.  Use  a  soap  solution  or  other  preferred
means.  Do  not  use  matches,  candles,  or  other  sources  of
ignition  to  check  for  gas  leaks.

NOTE−In  case  emergency  shut  down  is  required,  turn  off
the  main  manual  shut−off  valve  and  disconnect  main
power  to  unit.  These  devices  should  be  properly  labeled
by  the  installer.

Summary of Contents for Humiditrol L Series

Page 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Page 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Page 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Page 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Page 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Page 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Page 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Page 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Page 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Page 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Page 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Page 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Page 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Page 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Page 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Page 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Page 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Page 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Page 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Page 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Page 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Page 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Page 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Page 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Reviews: