background image

Page 21

Reheat  Operation  −  General

The  following  conditions  must  be  met  before  reheat  will  be

energized:

  1− Blower  must  be  operating.

  2− System  must  be  in  occupied  mode.

  3− System  must  NOT  be  operating  in  heating  mode.

  4− One  cooling  demand  is  required  if  the  unit  has  been

in  heating  mode,  the  IMC  has  been  reset,  or  at  initial

unit  start−up.

Reheat  Operation  −  Default

Reheat  will  operate  as  shown  in  table  18.

IMPORTANT  −  Free  cooling  does  not  operate  during

reheat.  Free  cooling  will  operate  as  shown  in  the

IMC  manual.

TABLE  18

Reheat  Operation

T’stat  and  HuE

midity  Demands

Operation

Reheat  Only

Compressor  Reheat

Reheat  &  Y1

Compressor  Cooling*

*If  there  is  no  reheat  demand  and  outdoor  air  is  suitable,
free  cooling  will  operate.

Combination  of  Demands

Table  18  shows  unit  operation  at  reheat  and  thermostat

demands.  The  following  examples  show  unit  operation

when  reheat  and  thermostat  demands  overlap.

  1− Compressor  is  operating  (Y1)  and  a  reheat

demand  is  initiated:

No  change  in  operation.

  2− Compressor  reheat  is  operating  and  a  Y1  cooling

demand  is  initiated:

Compressor  does  not  de−energize;  L14  reheat  valve

is  de−energized  for  compressor  cooling.

  3− Compressor  reheat  is  in  operation  and  outdoor

air  is  suitable  for  free  cooling;  then  reheat

demand  is  satisfied:

Free  cooling  is  energized  and  compressor  is

de−energized.

Service

The  unit  should  be  inspected  once  a  year  by  a  qualified
service  technician.

WARNING

Product  contains  fiberglass  wool.

Disturbing  the  insulation  in  this  product  during
installation,  maintenance,  or  repair  will  expose  you
to  fiberglass  wool.  Breathing  this  may  cause  lung
cancer.  (Fiberglass  wool  is  known  to  the  State  of
California  to  cause  cancer.)

Fiberglass  wool  may  also  cause  respiratory,  skin,
and  eye  irritation.

To  reduce  exposure  to  this  substance  or  for  further
information,  consult  material  safety  data  sheets
available  from  address  shown  below,  or  contact
your  supervisor.

P.O.  Box  799900

Dallas,  TX  75379−9900

A−Lubrication

All  motors  and  blower  shaft  bearings  are  prelubricated.
No  further  lubrication  is  needed.

B−Filters

Unit  is  equipped  with  two  16  X  25  X  2"  pleated  throw−away
type  filters.  Filters  should  be  checked  and  replaced  when
necessary.  See  figure  22.

NOTE−Filters  must  be  U.L.C.  certified  or  equivalent  for
use  in  Canada.

FIGURE  22

FILTER  REMOVAL

Summary of Contents for Humiditrol L Series

Page 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Page 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Page 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Page 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Page 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Page 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Page 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Page 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Page 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Page 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Page 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Page 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Page 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Page 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Page 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Page 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Page 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Page 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Page 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Page 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Page 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Page 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Page 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Page 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Reviews: