background image

Page 7

Electrical  Connections  −  Power  Supply

Do  not  apply  power  or  close  disconnect  switch  until
installation  is  complete.  Refer  to  start−up  directions.  Refer
closely  to  unit  wiring  diagram.

Refer  to  unit  nameplate  for  minimum  circuit  ampacity  and
maximum  overcurrent  protection.

  1− All  units  are  factory  wired.  For  208V  supply,

disconnect  the  orange  wire  (230V)  at  control  power
transformer.  Reconnect  the  red  wire  (208V).  Tape  the
exposed  end  of  the  230V  orange  wire.

Units  Without  Optional  Disconnect

  1− The  unit  is  provided  with  power  entry  knockouts

through  the  base  and  the  blower  section  mullion  (see
page  1).

  2−

Horizontal  Power  Entry

  −  Remove  necessary

electrical  knockouts  on  blower  section  mullion.

Bottom  Power  Entry 

− 

Route  wires  through  knockout  on  power  entry  cover.

NOTE  −  It  may  be  necessary  to  punch  larger  holes  for
power  wiring  (refer  to  current  NEC/CEC  requirements).

  3− Install  adequate  disconnect  switch  external  to  unit  in

accordance 

with 

local 

or 

national 

codes 

as

applicable.

Units  With  Factory−Installed  GFI

  1− Remove  necessary  electrical  knockouts  in  unit.

  2− Make  power  wiring  connections  in  bottom  power

entry  box.

  3− Connect  separate  120v  wiring  to  GFCI  outlet  pigtails

in  handy  box  on  front  left  corner  mullion.

Electrical  Connections  −  Control  Wiring

A−Thermostat  Location

Room 

thermostat 

mounts 

vertically 

on 

any

non−conductive  flat  surface.

Locate  thermostat  approximately  5  feet  (1.5m)  above  the
floor  in  an  area  with  good  air  circulation  at  average
temperature.  Avoid  locating  the  room  thermostat  where  it
might  be  affected  by:

−drafts  or  dead  spots  behind  doors  and  in  corners
−hot  or  cold  air  from  ducts
−radiant  heat  from  sun  or  units
−concealed  pipes  and  chimneys

B−Control  Wiring

  1− Route  thermostat  cable  or  wires  from  subbase

through  conduit  provided  in  unit.  Refer  to  wiring
diagram  on  unit.  For  thermostat  wire  runs  up  to  60  feet
(18m),  use  18  gauge  wire.  For  60  to  90  feet  (18  to
27m)  runs,  use  16  gauge  wire.

  2− Install 

thermostat 

and 

humidity 

sensor 

in

accordance 

with 

instructions 

provided 

with

thermostat  or  sensor.  See  figure  11  to  wire  units  set
in  local  thermostat  mode.  See  figure  12  for  units
wired  in  zone  sensor  mode.

  2− Install  thermostat  assembly  in  accordance  with

instructions  provided  with  thermostat.

IMPORTANT−Terminal  connections  at  the  wall  plate  or
subbase  must  be  made  securely.  Loose  control  wire
connections  may  allow  unit  to  operate  but  not  with  proper
response  to  room  demand.

C−Commercial  Controls  Platform

Units  without  an  optional  factory−installed  control  system
may  use  a  variety  of  different  temperature  control  systems.
The  unit  has  a  pre−wired  jack−plug  platform  allowing  a
variety  of  control  systems  to  Hplug−in"  to  unit  jack−plugs.
Control  systems  which  have  the  mating  commercial
controls  platform  jack−plug  contain  a  control  system  wiring
diagram  HC"  section.  This  diagram  section  is  used  with  unit
and  accessory  diagram  sections  for  total  system
operation.  Affix  diagrams  to  unit  in  alpha−numeric  order  as
shown  in  figure  10.  Refer  closely  to  installation  instructions
provided  with  each  temperature  control  system  for  proper
unit  operation.

FIGURE  10

COMPLETE  SYSTEM  DIAGRAM

HA"

Heating

Section

HB"

Unit

Section

HC"

Control

Section

HD"

Economizer

Section

Summary of Contents for Humiditrol L Series

Page 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Page 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Page 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Page 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Page 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Page 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Page 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Page 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Page 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Page 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Page 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Page 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Page 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Page 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Page 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Page 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Page 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Page 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Page 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Page 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Page 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Page 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Page 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Page 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Reviews: