Page 4

  5− Units  require  support  along  all  four  sides  of  unit  base.

Supports  must  be  constructed  of  steel  or  suitably
treated  wood  materials.

NOTE−When  installing  the  unit  on  a  combustible  surface
for  downflow  discharge  applications,  the  LARMF  roof
mounting  frame  is  required.

C−Horizontal  Discharge  Applications

  1− Specified  installation  clearances  must  be  maintained

when  mounting  units.  Refer  to  figure  3.

  2− Top  of  support  slab  should  be  at  least  4"  (102mm)

above  the  finished  grade  and  located  so  no  run−off
water  from  higher  ground  can  collect  around  the  unit.

  3− Units  are  shipped  in  downflow  position.  Convert  to

horizontal  discharge  as  follows:

a−Remove  horizontal  return  air  cover  and  rear  heat
section  panel.

b−Secure  horizontal  return  air  cover  over  downflow
return  air  opening.

c−Remove  horizontal  supply  air  cover  from  rear  heat
section  panel.  Cut  insulation  to  match  horizontal
supply  air  opening.  Use  foil  tape  to  secure  cut  edges
of  insulation  to  supply  air  opening.  Secure  horizontal
supply  air  cover  over  downflow  supply  air  opening.
Replace  rear  heat  section  panel.

  4− Units  require  support  along  all  four  sides  of  unit  base.

Supports  must  be  constructed  of  steel  or  suitably
treated  wood  materials.

NOTE  −  Securely  fasten  roof  frame  to  roof  per  local  codes.

Duct  Connection

All  exterior  ducts,  joints,  openings  in  roof  or  building  walls
must  be  insulated  and  weather−proofed  with  flashing  and
sealing  compounds  in  accordance  with  applicable  codes.
Any  duct  passing  through  an  unconditioned  space  must
be  insulated.

CAUTION

In  downflow  applications,  do  not  drill  or  punch
holes  in  base  of  unit.  Leaking  in  roof  may  occur  if
unit  base  is  punctured.

Rigging  Unit  For  Lifting

Rig  unit  for  lifting  by  attaching  four  cables  to  holes  in  unit
base  rail.  See  figure  4.

  1− Detach  wooden  base  protection  before  rigging.

  2− Connect  rigging  to  the  unit  base  using  both  holes  in

each  corner.

  3− All  panels  must  be  in  place  for  rigging.

  4− Place  fieldEprovided  HEstyle  pick  in  place  just  above

top  edge  of  unit.  Frame  must  be  of  adequate
strength  and  length.  (H−style  pick  prevents  damage
to  top  of  unit.

UNIT

WEIGHT

UNIT

LBS. KGS.

LGA036

841

382

LGA048

925

420

LGA060

935

424

LCA036

830

377

LCA048

860

390

LCA060

870

395

FIGURE  4

CAUTION  −  Do  not

walk  on  unit.

IMPORTANT  −  ALL

PANELS  MUST  BE  IN

PLACE  FOR  RIGGING.

RIGGING

LIFTING  POINT  SHOULD

BE  DIRECTLY  ABOVE
CENTER  OF  GRAVITY

*Maximum  weight  with  all  availE
able  factory−installed  accessories.

Summary of Contents for Humiditrol L Series

Page 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Page 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Page 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Page 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Page 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Page 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Page 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Page 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Page 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Page 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Page 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Page 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Page 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Page 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Page 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Page 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Page 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Page 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Page 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Page 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Page 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Page 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Page 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Page 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Reviews: