BMS ADDRESS TABLES
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 32
CL50-CHILLER-IOM_CUST-0808-E
LonWorks
LOGICAL DATA
Type
BM50
Index
Name NV
Type NV Direction Index
Description
DS50
DGT
1
I_Sp_On_Unit
95
input
415
DGT
1
O_Sp_On_Unit
95
output
415
[On / Off] Unit
3111
DGT
2
I_Sp_Reset
95
input
416
DGT
2
O_Sp_Reset
95
output
416
[Reset] Discharges the safety measures of the unit
3113
DGT
3
I_Sp_Unoc
95
input
417
DGT
3
O_Sp_Unoc
95
output
417
[BMS] Activation of the Inoccupation mode [Off]
occupation mode - [On] inoccupation mode
3925
DGT
17
O_Od_Alarm
95
output
431
[Alarm] General
1000
DGT
18
O_Od_Pump_1
95
output
432
[On/Off] Pump, 1
2615
DGT
19
O_Od_Pump_2
95
output
433
[On/Off] Pump, 2
2616
DGT
20
O_Od_Comp_11
95
output
434
[On/Off] Compressor 1, Circuit 1
2316
DGT
21
O_Od_Comp_21
95
output
435
[On/Off] Compressor 2, Circuit 1
2326
DGT
22
O_Od_Comp_13
95
output
436
[On/Off] Compressor 3, Circuit 1
2336
DGT
23
O_Od_CompHPump_1
95
output
437
[On/Off] Compressor, Heat pump, Circuit 1
2317
DGT
24
O_Od_Comp_12
95
output
438
[On/Off] Compressor 1, Circuit 2
2346
DGT
25
O_Od_Comp_22
95
output
439
[On/Off] Compressor 2, Circuit 2
2356
DGT
26
O_Od_Comp_23
95
output
440
[On/Off] Compressor 3, Circuit 2
2366
DGT
27
O_Od_CompHPump_2
95
output
441
[On/Off] Compressor, Heat pump, Circuit 2
2347
DGT
28
not used
95
output
442
not used
DGT
29
not used
95
output
443
not used
DGT
30
not used
95
output
444
not used
DGT
31
not used
95
output
445
not used
ANALOGIC DATA
Type
BM50
Index
Name NV
Type NV Direction Index
Description
DS50
ANL
1
I_Sp_WCool_1_BMS
105
input
1
ANL
1
O_Sp_WCool_1_BMS
105
output
1
[Occupation][Water SP] Required water temperature
in °C Cooling set point
3321
BMS
ANL
2
I_Sp_WHeat_1_BMS
105
input
2
ANL
2
O_Sp_WHeat_1_BMS
105
output
2
[Occupation][Water SP] Required water temperature
in °C Heating set point
3331
BMS
ANL
3
I_Sp_WCool_1_Uno
105
input
3
ANL
3
O_Sp_WCool_1_Uno
105
output
3
[Inoccupation][Water SP] Required water
temperature in °C Cooling set point
3321
Uno
ANL
4
I_Sp_WHeat_1_Uno
105
input
4
ANL
4
O_Sp_WHeat_1_Uno
105
output
4
[Inoccupation][Water SP] Required water
temperature in °C Heating set point
3331
Uno
ANL
17
O_Ia_TEEG
105
output
17
[Temperature] Inlet, Water
2112
ANL
18
O_T_Outside
105
output
18
[Temperature] Outdoor, Air
2111
ANL
19
O_Ia_TSEG
105
output
19
[Temperature] Outlet, Water
2113
ANL
20
O_Ia_P_HP_1
105
output
20
[Pressure] High, Circuit 1 (Bar)
2125
ANL
21
O_Ia_P_BP_1
105
output
21
[Pressure] Low, Circuit 1 (Bar)
2126
ANL
22
O_Ia_P_HP_2
105
output
22
[Pressure] High, Circuit 2 (Bar)
2135
ANL
23
O_Ia_P_BP_2
105
output
23
[Pressure] Low, Circuit 2 (Bar)
2136
ANL
24
not used
105
output
24
not used
ANL
25
not used
105
output
25
not used
ANL
26
not used
105
output
26
not used
ANL
27
not used
105
output
27
not used