BMS ADDRESS TABLES
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 31
CL50-CHILLER-IOM_CUST-0808-E
3FH
63
R
10 = 1.0
[Alarm]
bit.0 = Flow switch
bit.1 = High Temperature, Outlet
bit.2 = Low Temperature, Inlet
bit.3 = Low Temperature, Outlet
bit.4 = High Temperature, Inlet
bit.5 = Pump, 1
bit.6 = Pump, 2
bit.7 = Real Time Clock
bit.8 = BE50
bit.9 =
not used
bit.10 = Probes & Sensors
bit.11 = Fans, Condenser, Circuit 1
bit.12 = Fans, Condenser, Circuit 2
bit.13 = Fans, Condenser, Circuit 3
bit.14 =
not used
bit.15 =
not used
40H
64
R
10 = 1.0
[
Alarm]
bit.0 = Compressor, Circuit 1, Electric Protection
bit.1 = Compressor, Circuit 1, High Pressure
bit.2 = Compressor, Circuit 1, Low Pressure or Freeze
protection
bit.3 = Compressor, Circuit 2, Electric Protection
bit.4 = Compressor, Circuit 2, High Pressure
bit.5 = Compressor, Circuit 2, Low Pressure or Freeze
protection
bit.6 =
not used
bit.7 =
not used
bit.8 =
not used
bit.9 =
not used
bit.10 =
not used
bit.11 =
not used
bit.12 = Compressor, Circuit 1, Electronic Expansion Valve
bit.13 = Compressor, Circuit 2, Electronic Expansion Valve
bit.14 =
not used
bit.15 =
not used