BMS ADDRESS TABLES
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 29
CL50-CHILLER-IOM_CUST-0808-E
ANALOGIC DATA
@ (hexa)
@ (deci)
R/W
Unit
Description
DS50
01H
1
R/W
1 = 1 s
[ BMS ] Activation of the control by a computer or an automat.
Mode BMS is activated if this value is different from zero.
This value is decreased every second.
3934
02H
2
R/W
1 = 1
[Unit] without pump: 0=Started; 1=Stopped
[Unit] with pump: 1=Stopped; 2:P1 Only; 3=P2 Only; 4=P1-N P2-S;
5=P2-N P1-S; 6=P1/P2 by clock
3711
BMS
03H
3
R/W
1 = 1
[Unit] Change-over:
0=Cool. Only; 1=Heat. Only; 2=Auto. Pump; 3=Auto. No Pump
3311
BMS
04H
4
R
1 = 1
not used
05H
5
R/W
10 = 1.0°c
[Occupation][Water SP]
Required water temperature in °C Cooling set point.
3321
BMS
06H
6
R/W
10 = 1.0°c
[Occupation][Water SP]
Required water temperature in °C Heating set point.
3331
BMS
07H
7
R/W
10 = 1.0°c
[Inoccupation][Water SP]
Required water temperature in °C Cooling set point.
3321
Uno
08H
8
R/W
10 = 1.0°c
[Inoccupation][Water SP]
Required water temperature in °C Heating set point.
3331
Uno
09H
9
R
not used
0AH
10
R
not used
0BH
11
R
not used
0CH
12
R/W
1 = 1h
[Clock] Hour
3121
0DH
13
R/W
1 = 1m
[Clock] Minute
3122
0EH
14
R/W
1 = 1
[Clock] Day of the month
3123
0FH
15
R/W
1 = 1
[Clock] Month
3124
10H
16
R/W
1 = 2001
[Clock] Year
3125
11H
17
R/W
10 = 1.0°c
[BMS] Outlet temperature coming from the BMS.
12H
18
R/W
not used
13H
19
R/W
10 = 1.0°c
[BMS] Outdoor temperature coming from the BMS.
14H
20
R/W
not used
15H
21
R/W
not used
16H
22
R/W
not used
17H
23
R/W
not used
18H
24
R/W
not used
19H
25
R/W
not used
1AH
26
R/W
not used
1BH
27
R/W
not used
1CH
28
R/W
not used
1DH
29
R/W
not used
1EH
30
R/W
not used
1FH
31
R/W
not used
20H
32
R/W
not used
21H
33
R
1 = 1
[Alarm] Code Error
…
22H
34
R
10 = 1.0°c
[Temperature] Inlet, Water
2112
23H
35
R
10 = 1.0°c
[Temperature] Outdoor, Air
2111