BMS ADDRESS TABLES
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 33
CL50-CHILLER-IOM_CUST-0808-E
INTEGER DATA
Type Index
Name NV
Type NV Direction Index
Description
DS50
INT
1
I_Sp_BMS_Dog
8
input
208
INT
1
O_Sp_BMS_Dog
8
output
208
[ BMS ] Activation of the control by a computer or an
automat - mode BMS is activated if this value is different
from zero, This value is decreased every second
3934
INT
2
I_Sp_RunUnit_BMS
8
input
209
INT
2
O_Sp_RunUnit_BMS
8
output
209
[Unit] without pump: 0=Started; 1=Stopped
[Unit] with pump: 1=Stopped; 2:P1 Only; 3=P2 Only; 4=P1-
N P2-S; 5=P2-N P1-S; 6=P1/P2 by clock
3711
(BMS)
INT
3
I_Sp_ChOver_BMS
8
input
210
INT
3
O_Sp_ChOver_BMS
8
output
210
[Unit] Change-over: 0=Cool. Only; 1=Heat. Only; 2=Auto.
Pump; 3=Auto. No Pump
3311
BMS
INT
4
I_Sp_Rotat_BMS
8
input
211
INT
4
O_Sp_Rotat_BMS
8
output
211
[Unit] Activation of the circuits: 0=C1 Only; 1=C2 Only;
2=C1/C2 by clock
3411
(BMS)
INT
17
O_Error_Codes
8
output
224
[Alarm] Code Error
1000
INT
18
not used
81
output
225
not used
INT
19
not used
81
output
226
not used
INT
20
not used
81
output
227
not used
INT
21
not used
81
output
228
not used
INT
22
O_Error_Bits_1
8
output
229
[Alarm]
bit.0 = Flow switch
bit.1 = High Temperature, Outlet
bit.2 = Low Temperature, Inlet
bit.3 = Low Temperature, Outlet
bit.4 = High Temperature, Inlet
bit.5 = Pump, 1
bit.6 = Pump, 2
bit.7 = Real Time Clock
bit.8 = BE50
bit.9 =
not used
bit.10 = Probes & Sensors
bit.11 = Fans, Condenser, Circuit 1
bit.12 = Fans, Condenser, Circuit 2
bit.13 = Fans, Condenser, Circuit 3
bit.14 =
not used
bit.15 =
not used
INT
23
O_Error_Bits_2
8
output
230
[Alarm]
bit.0 = Compressor, Circuit 1, Electric Protection
bit.1 = Compressor, Circuit 1, High Pressure
bit.2 = Compressor, Circuit 1, Low Pressure or Freeze
protection
bit.3 = Compressor, Circuit 2, Electric Protection
bit.4 = Compressor, Circuit 2, High Pressure
bit.5 = Compressor, Circuit 2, Low Pressure or Freeze
protection
bit.6 =
not used
bit.7 =
not used
bit.8 =
not used
bit.9 =
not used
bit.10 =
not used
bit.11 =
not used
bit.12 = Compressor, Circuit 1, Electronic Expansion Valve
bit.13 = Compressor, Circuit 2, Electronic Expansion Valve
bit.14 =
not used
bit.15 =
not used