ALLOCATION OF DISPLAYS TO THE BM50
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 16
CL50-CHILLER-IOM_CUST-0808-E
Function
Ensure there is a good connection between the BM50 and its displays
Description
For each Climatic™50 card the fol
lowing setting must be made using the DS50.
Disconnect the pLan bus at J10 and J11 and connect the DS50, directly to J10 of the BM50;
Sds.1
Sds.5
Sds.6 (for the DC50)
Access the configuration mode by pressing buttons
,
for at least 5 seconds until the Sds.1 screen appears:
Press the button
to position the cursor over the ‘Setting’ line
Press button
again to position the cursor over the ‘I/O board adress’ line
With button
or
replace ‘
- -
‘ with the address of the BM50 connect
ed
and confirmed with button
The Sds.5 screen appears.
Press button
The Sds.6 screen appears.
The field "P:XX " shows the selected pLan address. In this example the value
"01" has been selected.
The fields in the "Adr" column represent the addresses of the terminal
displays associated with this BM50, while the "Priv/Shared" column indicates
the status of the selected terminal.
Pr: Private
Sh: Shared
Sp: Shared Printer (N/A)
Move the cursor from field to field using button
Select the value desired using button
or
.
To exit the configuration procedure and save the data, select the "OK?No",
field, choose "Yes" using buttons
or
and confirm by
pressing
Trm1
is reserved to allocate the
DC50
to the BM50.
Its value differs depending on the pLan address of the BM50
(See the opposite table)
Its status is always ‘Pr’
Trm3
is reserved to allocate the
DS50
to the BM50.
Its value is always 32
Its status is always ‘Sh’
pLan address
of the BM50
Trm1
DC50
1
17 pr
2
18 pr
3
19 pr
4
20 pr
If the terminal remains inactive (no button is pressed) for 30 seconds, the configuration procedure is aborted automatically.