CUSTOMIZED INPUT/OUTPUT
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 13
CL50-CHILLER-IOM_CUST-0808-E
Water set point cooling / heating 4-20mA signal:
The 4-20mA signal sent to the unit is linearly converted using the 2 water temperature set points. To increase the precision,
you can customize 2 range of water set point according to the cooling or heating mode operating.
Water set point offset 4-20mA signal:
The 4-20mA signal sent to the unit is linearly converted using a -5K to +5K range of temperature set point.
Free temperature probe connection:
Lennox NTC sensor:
The measured value will be displayed on following addresses (
2171
), (
2172
), (
2173
) or (
2174
).