CONFIGURATION OF THE BM50 pLAN ADDRESS
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 15
CL50-CHILLER-IOM_CUST-0808-E
Function
It may be necessary to change the address of the BM50 card on the pLan network
–
mainly in the case of Master/Slave
installation. To do this, use the following procedure:
Description
Set the address of the DS/DC50 display to 0:
Sds.1
Sds.2
Changing the address of BM50
Sds.3
Sds.4
Access the configuration mode by pressing the buttons
,
for at least 5 seconds until the Sds.1 screen appears:
Press button
to position the cursor over the ‘Setting’ line
With the
or
button, set the address of the display to 00 (instead of
the
standard value of 32) and confirm with button
The Sds.2 screen appears.
Switch the power supply to the BM50 card off, then on again after 5 seconds.
When the Sds.3 screen appears, press, the ‘Alarm’ and
buttons
for 5 seconds.
The Sds.4 screen appears.
Press the button
to position th
e cursor over the ‘pLan address’ line
. With
button
or
set the desired pLan address (1 to 12) and confirm with
button
.