36
INNOV@-pCO1-IOM-0907-E
MOP (High evaporation pressure, with integral time and adjustable threshold)
HiTcond (High condensation pressure that can be activated only by condensation
pressure
probe read by pCO, with integral time and adjustable threshold).
In the parameter table, the control parameters, with the thresholds and the default values, are described.
8.3.2 Accessories
SERIAL CARDS
The Rs485 serial card allows interfacing pCO1 boards directly to a Rs485 network. The maximum available
baud-rate corresponds to 19,200 (programmable by parameter). Connection with Rs485 network is executed
by connecting the extractible connector to the board displays. As for connections, refer to the instruction
sheet.
CLOCK CARD FOR pCO1
The clock option card allows managing the hour and date (day, month, year) for functions such as the time bands. The clock card
shall be inserted by removing the relevant port placed on its connector.
PCO200KEY0 HARDWARE KEY FOR pCO1
The hardware key allows downloading the application program to the pCO1 board in the place of the computer; furthermore, it also
allows uploading the Flash memory contents to the key.