32
INNOV@-pCO1-IOM-0907-E
PARAMETER DESCRIPTION
SCREEN
DEFAULT
SPECIAL VALUE
RANGE
UOM
High conductivity alarm threshold
Gb
2000
0-2000
uS/cm
Drain time as % of the manufacturer value
Gc
100
50-200
%
Drain frequency as % of the manufacture value
Gc
100
50-200
%
High pressure alarm set point
Gd
23.5
-99.9 - 99.9
bar
High pressure alarm differential
Gd
1.0
-99.9 - 99.9
bar
Condensing (pressure) setpoint
Ge
19.0
-99.9 - 99.9
bar
Condensing (pressure) differential
Ge
4.0
-99.9 - 99.9
bar
Modulating condensing fan speed-up time
Ge
30
0-999
seconds
Condensing (temperature) setpoint
Gf
55.0
-99.9 - 99.9
ºC / ºF
Condensing (temperature) differential
Gf
1.0
-99.9 - 99.9
ºC / ºF
Modulating condensing fan speed-up time
Gf
30
0-999
seconds
Maximum and Minimum condensing fan speed
Gg
10.0 / 0.0
0-10.0
Volt
Enable high pressure alarm Prevent function
Gh
Yes
No-Yes
bar
Prevent function set point (pressure)
Gh
20.0
-99.9 - 99.9
bar
Prevent function differential (pressure)
Gh
2.0
-99.9 - 99.9
bar
Enable high temperature alarm Prevent function
Gi
Yes
No-Yes
bar
Prevent function set point (temperature)
Gi
70.0
-99.9 - 99.9
ºC / ºF
Prevent function differential (temperature)
Gi
1.0
-99.9 - 99.9
ºC / ºF
Enable Master Control function
Gj
No
No-Yes
Rotation mode for units in pLAN network
Gk
Automatic
Automatic,
Timezones,
Running Hours
Number of units set in Standby mode
Gk
0
0-Number of unit in
Present/Rotat.
mode
Automatic rotation period for units in pLAN
Gk
24
1-240
Hours
Timezones rotation hour for units in pLAN network
Gl
22
0-23
Hours
Timezones rotation minutes for units in pLAN
network
Gl
00
0-59
minutes
Interval in days for timezones rotation in pLAN
network
Gl
3
1-7
days
Enable Force units by temperature in pLAN
network
Gm
No
No-Yes
Forcing delay for low and high ambient
temperature
Gm
3 / 3
0-999
minutes
Low room temp. diff. for forcing units in network
Gn
8
0-99.9
ºC / ºF
Low room temp. offset for forcing units in network
Gn
4
0-99.9
ºC / ºF
High room temp. diff. for forcing units in network
Go
8
0-99.9
ºC / ºF
High room temp. offset for forcing units in network
Go
4
0-99.9
ºC / ºF
Analog supply fan speed setting
Gp
80
0-100%
%
CAREL EXV DRIVERS
-->
Number of drivers connected
F0
0
0-2
Enable backup battery driver 1
F0
No
No-Yes
Enable backup battery driver 1
F0
No
No-Yes
Type of valve circuit 1
F1
10 (Carel E2V**P)
0-11
Superheating set point circuit 1
F1
6.0
2.0-50.0
ºC
Dead zone circuit 1
F1
0
0-9.9
ºC
Type valve circuit 2
F2
10 (Carel E2V**P)
0-11
Superheating set point circuit 2
F2
6.0
2.0-50.0
ºC
Dead zone circuit 2
F2
0
0-9.9
ºC
PID control
–
proportional gain circuit 1
F3
2.5
0.0-99.9
PID control
–
integration time circuit 1
F3
30
0-999
seconds
PID control
–
derivative time circuit 1
F3
5.0
0.0-99.9
seconds
PID control
–
proportional gain circuit 2
F4
2.5
0.0-99.9
PID control
–
integration time circuit 2
F4
30
0-999
seconds
PID control
–
derivative time circuit 2
F4
5.0
0.0-99.9
seconds
Threshold for low superheat protection circuit 1
F5
4.0
-4.0 - 10.0
ºC
Prot. threshold integration time, low superheat
circuit 1
F5
1.0
0-25.5
seconds
Threshold for low superheat protection circuit 2
F6
4.0
-4.0 - 10.0
ºC
Prot. threshold integration time, low superheat
circuit 2
F6
1.0
0-25.5
seconds
Percentage ratio between cooling capacity and
Driver capacity C 1
F7
30
0-100
%
Percentage ratio between cooling capacity and
Driver capacity C 2
F7
30
0-100
%
LOP threshold
F8
-40.0
-70.0 - 50.0
ºC
LOP threshold integration time
F8
4.0
0-25.5
seconds
MOP start delay
F9
30
0-500
seconds
MOP threshold
F9
16.0
-50.0 - 99.9
ºC