INNOV@-pCO1-IOM-0907-E
31
PARAMETER DESCRIPTION
SCREEN
DEFAULT
SPECIAL VALUE
RANGE
UOM
Minimum and maximum value measured by the
humidity probe
Ch
0.0 / 100.0
0-100.0
%RH
Enable pressure probe 1
Ci
No
No-Yes
Type of signal pressure probe 1
Ci
Current
0-1V, 0-10V,
Current
Minimum and maximum value pressure probe 1
Ci
0.0 / 30.0
-20.0 - 50.0
Bar
Enable pressure probe 2
Cj
No
No-Yes
Type of signal pressure probe 2
Cj
Current
0-1V, 0-10V,
Current
Minimum and maximum value pressure probe 2
Cj
0.0 / 30.0
-20.0 - 50.0
Bar
Room temperature probe type
Ck
NTC
NTC-PT1000
Enable supply air probe
Ck
Yes
No-Yes
Supply air temperature probe type
Ck
NTC
NTC-PT1000
Enable external temperature probe
Cl
No
No-Yes
External temperature probe type
Cl
NTC
NTC-PT1000
Enable recovery temperature probe
Cl
No
No-Yes
Recovery temperature probe type
Cl
NTC
NTC-PT1000
Enable condenser 1 temperature probe
Cm
No
No-Yes
Condenser 1 temperature probe type
Cm
NTC
NTC-PT1000
Enable condenser 2 temperature probe
Cm
No
No-Yes
Condenser 2 temperature probe type
Cm
NTC
NTC-PT1000
LAN unit configuration Unit 1 (U1)
Cn
Present/No rotat.
Present/Rotation
Present/No rotat.
Not present
LAN unit configuration Unit 2-3 (U2-U3)
Cn
Not present
Present/Rotation
Present/No rotat.
Not present
LAN unit configuration Unit 4-5-6 (U4-U5-U6)
Co
Not present
Present/Rotation
Present/No rotat.
Not present
LAN unit configuration Unit 7-8 (U7-U8)
Cp
Not present
Present/Rotation
Present/No rotat.
Not present
Enable analog fan on analog out 2
Cq
Yes
No-Yes
Enable expansion card
Cr
Off
Off-On
Enable expansion card alarm
Cr
Off
Off-On
Expansion card alarm delay
Cr
120
0-999
seconds
Reheating system
Cs
No Reheating
No Reheating,
Elect. Heaters, Hot
gas On/Off, Hot
gas modulat.
PARAMETERS
-->
Enable compressors/cooling battery together with
recovery valve
G0
No
No-Yes
Enable FIFO compressor rotation
G1
Yes
No-Yes
Temperature regulation type
G1
Prop.
Prop.-P+I
Logic of the capacity-control contact
G1
NC
NC-NO
Starting point to open modulating valve in cooling
(or single valve) with recovery (see G0)
G2
50.0
0.0-100.0
%
Starting and end point to open modulating valve in
cooling (or single valve)
G2
0.0 / 100.0
0.0-100.0
%
Starting point to open 3 position valve in cooling
(or single valve) with recovery (see G0)
G3
50,0
0.0-100.0
%
Starting and end point to open 3 position valve in
cooling (or single valve)
G3
0.0 / 100.0
0.0-100.0
%
Starting and end point to open modulating valve in
heating
G4
0.0 / 100.0
0.0-100.0
%
Starting and end point to open 3 position valve in
heating
G5
0.0 / 100.0
0.0-100.0
%
Starting and end point to open modulating valve in
recovery
G6
0.0 / 100.0
0.0-100.0
%
Minimum and maximum main fan speed
G7
0.0 / 10.0
0.0-10.0
Volt
Main fan speed during dehumidification
G7
5.0
0.0-10.0
Volt
Starting and end point to open modulating humid.
output
G8
0.0 / 10.0
0.0-10.0
Volt
Temperature differential to stop dehumidification
G9
5.0
0-99.9
ºC / ºF
Temperature offset to restart dehumidification
G9
4.0
0-99.9
ºC / ºF
Disable water drain for set point reduction
Ga
No
No-Yes
Disable drain for extended humidifier standby
Ga
No
No-Yes
Disable humidifier alarm messages
Ga
No
No-Yes
High conductivity pre-alarm threshold
Gb
1500
0-2000
uS/cm