INNOV@-pCO1-IOM-0907-E
29
PARAMETER DESCRIPTION
SCREEN
DEFAULT
SPECIAL VALUE
RANGE
UOM
Enable temperature / humidity / On-Off time
bands
K2
No / No / No
No-Yes
Start and end hour for On-Off time bands F1-1and
F1-2
K3
9 / 13 / 14 / 21
0-23
hours
Start and end minutes for On-Off time bands F1-1
and F1-2
K3
0 / 0 / 0 / 0
0-59
minutes
Start and end hour for On-Off time band F2
K4
14 / 21
0-23
hours
Start and end minutes for On-Off time band F2
K4
0 / 0
0-59
minutes
Select On-Off time bands (F1,F2,F3,F4) for each
day
K5
F3
F1-F2-F3-F4
Start hour temperature bands 1 and 2
K6
0 / 6
0-23
hours
Start minutes temperature bands 1 and 2
K6
0 / 0
0-59
minutes
Set point temperature bands 1 and 2
K6
23.0 / 23.0
see P1
ºC / ºF
Start hour temperature bands 3 and 4
K7
12 / 18
0-23
hours
Start minutes temperature bands 3 and 4
K7
0 / 0
0-59
minutes
Set point temperature bands 3 and 4
K7
23.0 / 23.0
see P1
ºC / ºF
Start hour humidity bands 1 and 2
K8
0 / 6
0-23
hours
Start minutes humidity bands 1 and 2
K8
0 / 0
0-59
minutes
Set point humidity bands 1 and 2
K8
50.0 / 50.0
see P2
%RH
Start hour humidity bands 3 and 4
K9
12 / 18
0-23
hours
Start minutes humidity bands 3 and 4
K9
0 / 0
0-59
minutes
Set point humidity bands 3 and 4
K9
50.0 / 50.0
see P2
%RH
Enter new Clock password
Ka
----
Setpoint Menu
Temperature set point
S1
23.0
see P1
ºC / ºF
Humidity set point
S1
50.0
see P2
%RH
User Menu
Enter user password
P0
----
0-9999
Minimum and maximum temperature set point
limits
P1
-99.9 / 99.9
-999.9-999.9
ºC / ºF
Minimum and maximum humidity set point limits
P2
0.0 / 100.0
0.0-100.0
%RH
Proportional temperature bands (differential) in
Heating and cooling
P3
3.0 / 3.0
0.0-100.0
ºC / ºF
Temperature dead zone (neutral zone)
P3
0,5
0.0-99.9
ºC / ºF
Proportional bands in Humidification and
Dehumidification
P4
2.0 / 2.0
0.0-99.9
%RH
Maximum production allowed, built-in humidifier
P4
70.0
0% -100%
% kg/h
Show language screen at start-up
P5
No
No-Yes
Switch unit off from button
P5
Yes
No-Yes
Enable remote On-Off digital input
P5
Yes
No-Yes
Recovery water temperature set point
P6
12,0
0-99.9
ºC / ºF
Recovery air temperature set point / Differential
P6
3.0 / 2.0
0-99.9
ºC / ºF
Enable compensation function
P7
No
No-Yes
Outside air compensation set point
P7
25.0
-999.9-999.9
ºC / ºF
Outside air compensation differential band
P7
3.0
-999.9-999.9
ºC / ºF
Offset maximum of compensation of the set of
temperature
P7
2.0
-999.9-999.9
ºC / ºF
High and low ambient temperature alarms offset
respect the setpoint
P8
10.0 / 10.0
-999.9-999.9
ºC / ºF
High and low ambient humidity alarms offset
respect the setpoint
P9
20.0 / 30.0
0-100,0
%RH
Enable outlet limit function
Pa
No
No-Yes
Outlet air set point for the limitation function
Pa
15.0
-999.9-999.9
ºC / ºF
Outlet air differential for the limitation function
Pa
5.0
-999.9-999.9
ºC / ºF
Assign type of alarm Serious/Minor AL01-AL20
Pb
All N
N-Y
Assign type of alarm Serious/Minor AL21-AL40
Pc
All N
N-Y
Assign type of alarm Serious/Minor AL41-AL60
Pd
All N
N-Y
Assign type of alarm Serious/Minor AL61-AL70
Pe
All N
N-Y
Board identification number for supervisory
network
Pf
1
0-200
Board communication speed for supervisory
network
Pf
1200
1200-19200
Baudrate
Serial communication protocol
Pf
Carel
Carel, Modbus,
Lon, RS232, Gsm
Telephone numbers entered on analogue modem
Pg
0
1-4
Enter telephone numbers on analogue modem
Pg
0
0…9,#,*,@,ˆ
Number of rings for GSM modem
Pg
0
0-9
Password to write SMS text message
Pg
0
0-9999
Destination GSM telephone number
Pg
0
0…9,#,*,@,ˆ