INNOV@-pCO1-IOM-0907-E
33
PARAMETER DESCRIPTION
SCREEN
DEFAULT
SPECIAL VALUE
RANGE
UOM
MOP threshold integration time
F9
4.0
0-25.5
seconds
High condensing temp. protection threshold
Fa
63.0
0-99.9
ºC
Integration time for high condensing temp.
threshold
Fa
4.0
0-25.5
seconds
High suction temperature threshold
Fb
30.0
0-100.0
ºC
Custom Valve: minimum steps
Fc
0
0-8100
Custom Valve: maximum steps
Fc
1600
0-8100
Custom Valve: closing steps
Fd
3600
0-8100
Custom Valve: return steps
Fd
0
0-8100
Custom Valve: enable extra step in opening
Fe
No
No-Yes
Custom Valve: enable extra step in closing
Fe
No
No-Yes
Custom Valve: operating current
Ff
250
0-1000
mA
Custom Valve: holding current
Ff
100
0-1000
mA
Custom Valve: frequency
Fg
100
32-330
Hertz
Custom Valve: duty cycle
Fg
50
0-100
%
Minimum evaporation pressure probe value
Fh
0.0
-9.9 - 10.0
Bar
Maximum evaporation pressure probe value
Fh
30.0
3.5 - 40.0
Bar
Low superheating alarm delay
Fi
0
0-3600
seconds
High suction temperature alarm delay
Fi
0
0-3600
seconds
LOP alarm delay
Fj
0
0-3600
seconds
MOP alarm delay
Fj
0
0-3600
seconds
TIMES
.-->
Supply fan start and stop delay
T0
10 / 20
0-999
seconds
Integration time for P+I temperature control
T1
600
0-999
seconds
Travel time for 3 position valve
T1
180
0-999
seconds
Low pressure alarm delay
T2
180
0-9999
seconds
High-low temperature-humidity alarm delays
T2
600
0-9999
seconds
Not serious alarm activation delay
T3
0
0-9999
seconds
Serious alarm activation delay
T3
0
0-9999
seconds
Air flow switch alarm delay
T4
10
0-9999
seconds
Water flow switch alarm delay
T4
10
0-9999
seconds
Minimum compressor off time
T5
180
0-9999
seconds
Minimum compressor on time
T5
60
0-9999
seconds
Delay between compressor starts
T6
360
0-9999
seconds
Minimum delay between starts of different
compressors
T6
10
0-999
seconds
Cap. control activation delay
T7
10
0-9999
seconds
Start delay between comps. of same circuit
T7a
30
0-999
seconds
Stop delay between comps. of same circuit
T7b
30
0-999
seconds
Heater start delay
T8
3
0-9999
seconds
INITIALISATION
.-->
Enter password for reset Default values function
V0
----
0-9999
Delete BASIC alarm log
V1
No
No-Yes
Enter new manufacturer password
V2
----
0-9999