45
Appendix 2 Problems and Solution
In case the UPS cannot work normally, it might be wrong in installation, wiring or operati-
on. Please check these aspects first. If all these aspects are checked without any problem,
please consult with local agent right away and provide below information.
1.
Product model name and serial number.
2.
Try to describe the fault with more details, such as LCD display info, LED lights
status, etc.
Read the user manual carefully, it can help a lot for using this UPS in the right way. Some
FAQ (frequently asked questions) may help you to troubleshoot your problem easily.
Problem
Possible reason
Solution
Utility is connected
but the UPS cannot be
powered ON.
Input power supply is
not connected;
Measure if the UPS input voltage/
frequency is within the window.
Check if UPS input is switched on
Utility normal but Utility
LED does not light on,
and the UPS operates at
battery mode
The input breakers
of the UPS are not
switched on;
Switch on the input breaker;
Make sure the input cable is well
connected.
The UPS does not
indicate any failure,
but output do not have
voltage
Output cable does
not well connected;
Make sure the output cable is well
connected;
Switch on the output breaker.
Utility LED is flashing
Utility voltage
exceeds UPS input
range.
If the UPS operates at battery
mode, please pay attention to the
remaining backup time needed for
your system.
Battery LED is flashing
but
no charge voltage and
current
Battery breaker
does not switch
on, or batteries
are damaged, or
battery is reversely
connected.
Battery number and
capacity are not set
correctly.
Switch on the battery breaker. If
batteries are damaged, need to
replace whole group batteries,
Connect the battery cables
correctly;
Go to LCD setting of the battery
number and capacity, set the
correct data.
Buzzer beeps every
0.5 seconds and
LCD display “output
overload”
Overload
Remove some load