22
ώ
Switch ON the output breaker.
ώ
Switch ON the input breaker.
The UPS powers from the static bypass instead of the maintenance bypass, then the
bypass LED will light up.
ώ
Switch OFF the maintenance bypass breaker, then the output is supplied by the static
bypass of the UPS.
ώ
Put on the maintenance switch cover.
The rectifier will operate normally after 30 seconds. If the inverter works normally, the
system will be transferred from bypass mode to normal mode.
ώ
Set the Battery Breaker to the “ON” for long run UPS.
ώ
Switch ON the power switch for standard UPS.
ώ
Turn on the Output switch.
ώ
Switch ON the power switch (power will feed to auxiliary power board).
ώ
Trigger the cold start button as the position 5 of the below drawing.
When battery normal, rectifier starts operation, 30s later, inverter starts and operates and
battery LED on
4.2.4 Cold start procedure
CAUTION:
Follow these procedures when the input AC Utility Failure, but
battery is normal
1
2
3
4
5
POWER