14
10kVA factory setting of the long-run unit is battery quantity---16pcs, battery capacit-
y---12V9AH (charger current 1.35A). When connecting 18/20 batteries, please re-set desi-
red battery quantity and its capacity after UPS starts at AC mode. Charger current could be
adjusted automatically according to battery capacity selected. All related settings can be
done through LCD panel or monitoring software
15-20kVA factory setting of the long-run unit is battery quantity---32pcs, battery capacit-
y---12V18AH (charger current 2.7A). When connecting 32/34/36/38/40 batteries, please re-
set desired battery quantity and its capacity after UPS starts at AC mode. Charger current
could be adjusted automatically according to battery capacity selected. All related settings
can be done through LCD panel or monitoring software
The following sections introduce the installation procedures specified
to the parallel system.
CAUTION:
Ensure correct polarity battery string series connection.
I.e. inter-tier and inter block connections are from (+) to
(-) terminals. Don’t mix batteries with different capacity
or different brands, or even mix up new and old batteries,
either.
WARNING:
Ensure correct polarity of string end connections to the
Battery Circuit Breaker and from the Battery Circuit
Breaker to the UPS terminals i.e. (+) to (+) / (-) to (-) but
disconnect one or more battery cell links in each tier. Do
not reconnect these links and do not close the battery
circuit breaker unless authorized by the commissioning
engineer.
3.9 UPS PARALLEL INSTALLATION
3.9.1 Cabinet installation
Connect all the UPS needed to be put into parallel system as below picture.
UPS1
UPS2
UPS3
UPS4
AC INPUT
AC OUTPUT