8. Turn on all the battery breaker and confirm the parameter (V/I) are normal.
9. Connected the Load, and check whether the output current is balance.
Switch on and off the utility breaker to test all the UPS converters system from Utility to
battery and restored function are working find
This section lists the event and alarm messages that the UPS might display. The messages
are listed in alphabetical order. This section is listed with each alarm message to help you
troubleshoot problems.
4.6 DISPLAY MESSAGES/TROUBLESHOOTING
Display messages
Operational Status and Mode(s)
Code
(St)
Information
stand for
LED
Fault
Bypass
Battery
Inverter
1
Initialized
EXTINGUISH
EXTINGUISH
EXTINGUISH
EXTINGUISH
2
Standby Mode
EXTINGUISH
EXTINGUISH
X
EXTINGUISH
3
No Output
EXTINGUISH
EXTINGUISH
X
EXTINGUISH
4
Bypass Mode
EXTINGUISH
LIGHT
X
EXTINGUISH
5
Utility Mode
EXTINGUISH
EXTINGUISH
X
LIGHT
6
Battery Mode
EXTINGUISH
EXTINGUISH
LIGHT
EXTINGUISH
7
Battery Self-diag-
nostics
EXTINGUISH
EXTINGUISH
LIGHT
EXTINGUISH
8
Inverter is starting
up
EXTINGUISH
X
X
EXTINGUISH
9
ECO Mode
EXTINGUISH
X
X
X
10
EPO Mode
LIGHT
EXTINGUISH
X
EXTINGUISH
11
Maintenance
Bypass Mode
EXTINGUISH
EXTINGUISH
EXTINGUISH
EXTINGUISH
12
Fault Mode
LIGHT
X
X
X
CAUTION: “X” means it is determined by other conditions