34
Periodical battery self-test set-
ting (note: the part in dashed box
flashes)
Battery temperature compensati-
on sensor switch setting
(Note: the information in the red
box will be flashing)
In the buzzer setting press “ON” or in parallel ID setting
press “OFF”, it goes to the battery self-test setting. In
the meantime the setting state flashes as above picture
shows (Note: ON 1- the battery self-test function is
enabled, UPS will do self-test 10 seconds every 30 days;
ON 2- the battery self-test function is enabled, UPS will
do self-test 10 minutes every 30 days; ON 3- the battery
self-test function is enabled, UPS will do self-test till
battery voltage reaches EOD point every 30 days; OF-
F-battery self-test function is disabled.).
1. Press “
” to set periodically self-test setting. The
options are OFF, ON 1, ON 2 and ON 3.
2. Press “ON” to exit Periodically Self-test setting and
save the setting value, and goes to battery tempera-
ture compensation sensor switch setting.
3. Press “OFF” to exit Periodically Self-test setting and
goes to buzzer setting.
Press “ON” under the periodical battery self-test setting
or press “OFF” under device address setting, goes to the
battery temperature compensation switch setting. The
setting state flashes as above picture shows (Note: OFF
means turn off the sensor switch, ON means turn on
the sensor switch, send query command to sensor with
address 11,12 every second.
1. Press “
” is to set the battery sensor, with options
OFF & ON.
2. Press “ON” to exit the battery sensor setting and
save the battery sensor setting value and transfer to
device address setting.
3. Press “OFF” to exit the battery sensor setting and
transfer to battery periodical battery self-test
setting.
4.4.9 Periodical battery self-test Setting
4.4.10 Battery temperature compensation sensor switch setting
Summary of Contents for STARK 10 kVA
Page 51: ...51 ...
Page 52: ...www informups com ...