13: Maintenance
SLC™ Console Manager User Guide
218
2.
Enter the following:
Internal Temperature
Site Information
SLC Firmware
Reboot
Select this option to reboot the SLC console manager immediately. The default is
No
.
Note:
The front panel LCD displays the “Rebooting the SLC” message, and the
normal boot sequence occurs.
Shutdown
Select this option to shut down the SLC unit. The default is
No
.
Current
Displays current temperature.
Low (°C)
Sets the acceptable minimum for the internal temperature of the SLC console
manager. If the temperature of the SLC device changes to be outside of this
range, the unit will issue an SNMP trap.
High (°C)
Sets the acceptable maximum for the internal temperature of the SLC device. If
the temperature of the SLC unit changes to be outside of this range, the SLC
device will issue an SNMP trap.
Calibrate Offset (°C)
An offset for calibrating the internal temperature of the SLC console manager. The
offset will be applied one hour after setting the calibration value. Zeroing the
offset will take effect immediately and will cancel any current and/or pending
calibration.
Data Center Rack Row
Set these fields to define the rack row the SLC unit is located within a large data
center. The default for these fields is 1.
Data Center Rack
Cluster
Set these fields to define the rack cluster the SLC device is located within a large
data center. The default for these fields is 1.
Data Center Rack
Set these fields to define the rack the SLC console manager is located within a
large data center. The default for these fields is 1.
Current Version
Displays the current firmware version.
Update Firmware
To update the SLC firmware, select the checkbox. If you select this option, the
SLC unit reboots after you apply the update. The first time boot for each bank
may take up to 5 minutes. Subsequent boot times will be approximately 2
minutes.
To view a log of all prior firmware updates, click the
Firmware Update Log
link.
Note:
For dual boot units, the non-active boot bank is updated during the
firmware update, without requiring a reboot. The configuration on the current boot
bank may optionally be copied to the non-active boot bank during the firmware
update.
Firmware Filename
The name of the firmware update file downloaded from the Lantronix web site.
Key
A key for validating the firmware file. The key is provided with the firmware file
(32 hex characters).
Load Firmware via
From the drop-down list, select the method of loading the firmware. Options are
FTP, SFTP, TFTP, HTTP, NFS, USB
and
PC Card
.
FTP
is the default. For
NFS
,
the mount directory must be specified. For
PC Card
, the slot must be selected.
Connections available depend on the model of the SLB or SLC unit.