DISPENSER INSTALLATION HIGHLIGHTS

This unit has been factory sanitized per Lancer specifications.

Listed below are six critical elements which will aid in a successful installation.

1.   Fill water bath until water overflows from tank overflow tube.

2.   The carbonator pump motor must be disconnected from the power supply (see Section 1.7) prior to connection to 

water supply for initial build up of ice bank. Failure to do so will result in automatic shut off of carbonator (see item 
6 below) or damage to the pump.

3.   If this dispenser is installed in an area that is susceptible to ±10% variation of the nominal line voltage, consider  

installing a surge protector or similar protection device.

4.   There is a five (5) minute delay which prevents the compressor and condenser fan from starting until the delay 

has lapsed. If electrical current is interrupted, there is always a five (5) minute delay before the compressor starts.

5.   Supply Water Pressure: Minimum - 25 PSI (0.172 MPA); Maximum - 50 PSI (0.345 MPA);  If pressure is over 50 

PSIG (0.345 MPA), a water pressure regulator must be used.

6.   On units with the built in water regulator, the regulator must be removed if inlet water pressure is less than 25 

PSIG. 

(0.172 MPA)

PUNTOS IMPORTANTES EN LA UNIDAD DISPENSADORA 

Esta unidad ha sido saneada en fabrica por las especificaciones de Lancer.

A continuacion se relacionan 6 puntos importantes para una connecta instalacion.

1.   Llene  el  bano-Maria  hasta  que  el  agua  se  desborde  sobre  el  tubo  que  controla  la  derrama  del  tanque.
2.   El motor de la bomba del carbonatador debe desconectarse electricamente (Ver Manual - Seccion 1.7) antes 

de conectar el suministro de agua para la formacion inicial del banco de hielo. De no hacerse esto resultaria en 

un bloqueo automatico del carbonatador (ver abajo el punto 6) o en danos a la bomba.

3.   Si la unidad va a ser instalada en un area en la que puedan darse variaciones de voltage de + 6 - 10% de su 

valor nominal, se debe considerar la conveniencia de instalar un estabilizador de corriente o sistema de 
proteccion similar.

4.   Hay una demora de 5 minutos que evita que el compresor y el abanico del condensador arranquen hasta pasado 

ese tiempo. Si hay algun corte en la corriente electrica siempre se producira esa demora de 5 minutos antes de 
arrancar el compresor.

5.   Presión de suministro del agua de red: Minimo 25 PSI (0.172 MPA); Maximo 50 PSI (0.345 MPA). En unidades 

sin regulador de presión incorporado, si la presión del agua es superior a 50 PSIG (0.345 MPA) se debe usar un 
regulador de presión.

6.   En unidades con regulador de presión incorporado, el regulador debe der eliminado cuando la presión de entrada 

de agua sea inferior a 25 PSIG (0.172 MPA).

REGLES DE SECURITE POUR L’NSTALLATION DU DISTRIBUTEUR DE SODAS 

La proprètè da cet ensamable est assurè à I’usine sulvant les spècifications èmis par Lancer .

Il est essentiel de respecter les 6 points suivants pour l’installation de l’appareil:

1.   Remplir le bain-Maire jusqu’a ce que l’eau dèborde par le tuyau de trop-plein du rèservoir.

2.   Le moteur de la pompe du carbonateur doit etre dèbranchè de l’alimentation èlectrique (Voir le manuel, 

Section 1.7) avant l’arrivèe de l’eau pour la formation initiale de la glace. Oublier ou nègliger cette opèration 

provoquera l’arret automatique du carbonateur (voir le point 6 cidessous) ou causera des dommages à la pompe.

3.   Si le distributeur es installè dans une zone ou la tension èlectrique nominale est susceptible de variations de (+) 

10%, il est conseillè d’installer un appaeil de protection contre les sautes de courant.

4.   Un d’lai de 5 minutes empeche le compresseur et la ventilation du condesateur de se mettre en marche avant 

que ce lees de temps ne se soit ècoulè. Lorsque le courant èlectrique es interrompu, il y a toujours un dèlai de 5 

minutes avant que le presseur ne se mette en.

5.   Pression de l’eau: Minimum 25 PSI (0.172 MPA); Maximo 50 PSI (0.345 MPA). Sur les unitès qui n’ont pas de 

règulateur de pression d’eau incorprè, si la pression d’H2O est supèrieure à 50 PSIG (0.345 MPA), un règulateur 

de pression d’eau doit etre utilsisè.

6.   Sur les unitès avec règulateur d’eau incorporè, le règulateur doit etre enlevè si la pression d’arrivve est inferièure 

à 25 PSIG (0.172 MPA)

!

!

!

!

!

!

Summary of Contents for Spartan

Page 1: ...chnical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com Manual PN 28 0936 NOVEMBER 2013 FOR QUALIFIED INSTALLER ONLY Spartan Dispenser Operation Manual PN 28 0936 Lancer is the re...

Page 2: ...G AND SANITIZING 15 3 1 GENERAL INFORMATION 15 3 2 CLEANING AND SANITIZING SOLUTIONS 15 3 3 AMBIENT PROCESS 16 3 4 NOZZLE CLEANING 16 4 TROUBLESHOOTING 16 24 5 DISPENSER DISPOSAL 24 6 TROUBLE SHOOTING...

Page 3: ...S AND WIRING DIAGRAMS 26 7 1 MAIN UNITASSEMBLY 26 7 2 PUMP ASSEMBLY 27 7 3 REFRIGERATION DECK ASSEMBLY 28 7 4 ELECTRICAL BOX ASSEMBLY 29 7 5 CARBONATOR ASSEMBLY 30 7 6 REFRIGERATION DECK WIRING DIAGRA...

Page 4: ...rating 127 lbs 57 5 kg ICE Capacity 8 11 lbs 3 6 5 0 kg FITTINGS Water for carbonator inlet 1 4 barb Plain water inlet 1 4 barb Brand syrup inlets 1 4 barb CO2 inlet 1 4 barb PLAIN WATER SUPPLY Min fl...

Page 5: ...Clamps Fittings Water Booster Water Regulator Precision Cutters if removing replacing carbonator tank CONSIDER LOCATION OF THE FOLLOWING PRIOR TO INSTALL Water supply lines Drain Is the countertop lev...

Page 6: ...cas sensoriales o mentales o por falta de experiencia y conocimientos que hayan recibido supervisi n o instrucciones relativas al uso del aparato de una manera segura y comprenda los peligros involucr...

Page 7: ...izador de corriente o sistema de proteccion similar 4 Hay una demora de 5 minutos que evita que el compresor y el abanico del condensador arranquen hasta pasado ese tiempo Si hay algun corte en la cor...

Page 8: ...ues locaux lorsque vous faites des connexions Chaque distributrice doit avoir un circuit lectrique s par N utilisez pas de cordons prolongateurs avec cet appareil Ne pas le brancher avec d autres appa...

Page 9: ...t is the responsibility of the installer to ensure compliance Proporcione un suministro adecuado de agua potable La l nea de suministro de agua debe ser de una tuber a de por lo menos 3 8 pulgadas 9 5...

Page 10: ...level front to back and side to side Place a level on the top of the rear edge of the dispenser The bubble must settle between the level lines Repeat this procedure for the remaining three sides Leve...

Page 11: ...sconnect the power supply to the carbonator motor by disconnecting the designated connector located near the top of the electrical control box on the refrigeration deck B Check the dispenser serial nu...

Page 12: ...llowing the manufacturer s instructions 1 10 PURGING THE CARBONATION SYSTEM A Turn on water source Lift the black lever on the top of the carbonator tank relief valve until water flows from the holes...

Page 13: ...the proper brix use screwdriver to adjust syrup flow control see Figure 1 C Once proper ratio is obtained repeat to verify D Remove syrup separator PN 54 0031 installed in Section 1 13 F above E Insta...

Page 14: ...sh in warm soapy water C Pour warm soapy water into the drip tray and wipe with a clean cloth D With a clean cloth and warm water wipe off all of the unit s exterior surfaces DO NOT USE ABRASIVE SOAPS...

Page 15: ...operation and sanitation requirements are maintained NOTE The cleaning procedures provided herein pertain to the Lancer equipment identified by this manual If other equipment is being cleaned follow t...

Page 16: ...syrup system again 3 4 NOZZLE CLEANING A Disconnect power so not to activate the valve while cleaning Remove nozzle and diffuser Wash these parts in cleaning solution then immerse them in a bath of s...

Page 17: ...rratic ratio A Incoming water and or syrup supply not at minimum flowing pressure B Foreign debris in water and or syrup flow controls A Check pressure and adjust B Remove flow controls from upper bod...

Page 18: ...or replace pump F Remove kink or replace line 4 9 No water just syrup Ice bank grew to water inlet line to carbonator tank A Low water bath level B Unit not level C Syrup in water bath D Water cage i...

Page 19: ...high C Water flow rate too high D Nozzle and diffuser not installed E Nozzle and diffuser not clean F Air in BIB lines G Poor quality ice H High beverage temperature A Correct prior to dispenser Cons...

Page 20: ...e H Transformer failure I Ice bank probe not connected properly to PCB A Allow for five 5 minute delay to lapse B Fill water reservoir until water flows from overflow tube C Reset breaker or replace f...

Page 21: ...robe H Reset transformer circuit breaker If breaker pops again refer to Sec 4 23 I Connect ice bank probe to PCB 4 17 Compressor does not start no hum but gas cooler fan motor runs A Compressor relay...

Page 22: ...low for minimum clearances of 8 inches 203 mm over top C Measure voltage across common and run terminal on compressor Voltage must not drop below 90 of rated voltage D Refer to wiring diagram and corr...

Page 23: ...BIB pump does not operate when dispensing valve opened A Out of CO2 CO2 not turned on or low CO2 pressure B Out of syrup C BIB connector not tight D Kinks in syrup or gas lines E Bad BIB Pumps A Repl...

Page 24: ...A Leak in discharge line or fittings B Empty BIB C Air leak on inlet line or bag connector A Repair or replace discharge B Replace BIB C Repair or replace 4 29 No product out light A Burned out lamp...

Page 25: ...d be continuity Remove wire from J2 connector There should be NO continuity from 2 to 1 c You should be able to hear the click sound of the relay closing when the time delays end H Turn electrical pow...