background image

18

Checking the Normal PCB Operation

THE ELECTRONIC ICE BANK CONTROL (EIBC)

 

 

Terminal block has AC line voltage and, when servicing the unit, should be covered with tape. Tape should cover bare 

electrical connections to prevent electrical shock.

WARNING

1.  Turn power OFF or insure that power has been               

disconnected from dispenser

2.  Check condition of 0.5 amp fuse at location shown in      di-

agram to the right. If fuse is blown, trace cause of short 

in valve wire harness and associated 24 VAC lines and 

replace fuse. If fuse is good, continue with next step.

3.  Disconnect leads from the terminal block that connect to the 

PCB, noting their specific location for reconnection.

4.  Disconnect both the Ice Bank probe (J2) and the            

Carbonator probe (J3) (if equipped) connections from 

board.

5.  Use a short copper wire, paper clip, or other means to short 

the Ice Bank probe terminals (J2) on the PCB by touching 

all three (3) pins together.

6.  Set Ohm test meter to measure continuity.
7.  Reconnect power or turn dispenser ON.
8.  Observe time and check continuity of the PCB screw lug 

connections:

9.  Turn electrical power OFF for 15 seconds and then back ON again to reset Carbonator timer. Again, measure continuity of the 

PCB screw lug connections

• 

Terminal 3 to 4 (Carbonator): During the first 2.5 to 

3.5 minutes there should be continuity. After 2.5 to 3.5 

minutes, there should be NO continuity.

• 

Terminal 2 to 1 (Compressor): During first 4 to 6 

minutes, there should be NO continuity. After 4 to 6 

minutes, there should be continuity. There should be 

NO continuity from 2 to 1. 

• 

You should be able to hear a “click” sound of the relay   

closing when the time delay ends.

• 

Terminal 3 to 4: There should be continuity. Use a short copper wire, paper clip, or other means to short the Carbonator 

probe terminals (J3) on the PCB by touching all three (3) pins together. This should be done before the 2.5 to 3.5 minute 

time limit has elapsed. Measure the continuity again between Terminal 3 to 4: There should be 

NO

 continuity.

10.  If all the above work as noted, then the board is functioning properly. Remove tape and reconnect board. If any non-conformities 

are found, the PCB must be replaced (PN 52-1423/01).

     

 

To prevent possible harm to the environment from improper disposal, recycle the unit  

 

 

   

by locating an authorized recycler or contact the retailer where the product was purchased.  

 

   

Comply with local regulations regarding disposal of the refrigerant and insulation.

   

Dispenser Disposal

Summary of Contents for CED-04

Page 1: ...demark of Lancer 2016 by Lancer all rights reserved 500 Lancer Corporation 6655 Lancer Blvd San Antonio Texas 78219 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancerc...

Page 2: ...s a hazardous situation which if not avoided will result in death or serious injury Be sure to read all Warning statements before proceeding with the installation WARNING Text following the Caution si...

Page 3: ...ualified personnel should service internal components of electrical control housing WARNING Make sure that all water lines are tight and units are dry before making any electrical connections If this...

Page 4: ...59 42 kg ELECTRICAL 115 VAC 60 Hz 5 0 Amps PLAIN WATER SUPPLY Min Flowing Pressure 50 PSIG 0 345 MPA CARBONATED WATER SUPPLY Min Flowing Pressure 25 PSI 0 172 MPA Max Static Pressure 50 PSI 0 345 MPA...

Page 5: ...r PN 82 3401 or MC 163172 Water Regulator recommended CONSIDER THE FOLLOWING BEFORE INSTALLATION Location of Water Supply Lines Location of Drain Location of Electrical Outlet Location of Heating and...

Page 6: ...location that is in close proximity to a properly grounded electrical outlet within five 5 feet 1 5 m of a drain and a water supply that meets the requirements shown in the Specifications section foun...

Page 7: ...sert water line into a large bucket and fill with approx 5 4 gallons 20 4 L of distilled water 9 Add 1 8 oz 4 g of baking soda to distilled water and stir A B C A Bucket B Distilled Water approx 5 4 g...

Page 8: ...l devices on the same outlet WARNING 19 Turn on the power switch at the top of the unit to turn on the unit and begin building an ice bank Installing Remote Syrup Pumps Bag in Box A B C A Syrup Pump B...

Page 9: ...ulk system 2 Connect a 1 4 nut stem and seal to CO2 regulator outlet Then connect tubing routed from tee at syrup pumps tanks A CO2 Regulator B Fitting C Line to CO2 Regulator Manifold D Oetiker Plier...

Page 10: ...oz in 4 sec Use a screwdriver to adjust if needed 3 Remove nozzle by twisting counter clockwise and pulling down then remove diffuser by pulling down 4 Install Lancer yellow syrup separator PN 54 003...

Page 11: ...IZING Lancer equipment new or reconditioned is shipped from the factory cleaned and sanitized in accordance with NSF guidelines The operator of the equipment must provide continuous maintenance as req...

Page 12: ...BIB s 2 Place syrup lines with BIB connectors in a bucket of warm water 3 Activate each valve to fill the lines with warm water and flush out syrup remaining in the lines 4 Prepare Cleaning Solution d...

Page 13: ...flow control 5 Bad syrup pump 1 Adjust CO2 pressure to 80 PSI 0 550 MPA minimum 70 PSI 0 480 MPA for BIB pumps 2 Replace CO2 tank refill 3 Open shutoff fully 4 Remove syrup flow control form upper bo...

Page 14: ...3 Melt ice bank Remove all water Refill Locate possible syrup leak area and repair 4 Reposition water cage 5 Find leak and recharge unit If unit is not frozen 6 Turn water ON and shut unit OFF 7 Turn...

Page 15: ...y 3 Refrigeration system not running 4 Refrigerant leak 5 Gas Cooler fan motor not working 6 Dirty Gas Cooler 7 Dispenser capacity exceeded 1 Check clearances around sides top and inlet of unit Remove...

Page 16: ...w 90 of rated voltage 2 Refer to wiring diagram and correct 3 Replace starting relay Be sure to use correct relay Failure to use correct relay will cause compressor failure Compressor starts and runs...

Page 17: ...upply or adjust CO2 pressure to 70 80 PSI 0 483 0 552 MPA 2 Replace syrup supply 3 Fasten connector tightly 4 Straighten or replace lines 5 Replace BIB pump BIB pump operated but no flow 1 Leak in syr...

Page 18: ...hen back ON again to reset Carbonator timer Again measure continuity of the PCB screw lug connections Terminal 3 to 4 Carbonator During the first 2 5 to 3 5 minutes there should be continuity After 2...

Page 19: ...19 INTENTIONALLY LEFT BLANK...

Page 20: ...20 04 05 06 09 16 18 10 01 02 03 07 08 11 12 13 15 14 17 ILLUSTRATIONS AND PART LISTINGS Main Unit Assembly...

Page 21: ...rup 1 CED 04 48 3551 Tube Assembly Syrup 2 CED 04 48 3550 Tube Assembly Syrup 3 CED 04 48 3572 Tube Assembly Syrup 4 CED 04 09 82 4563 Tank 10 82 0025 01 Leg Set 4 legs w o hardware 11 01 2115 01 Over...

Page 22: ...1553 01 Fan Motor Bracket 03 82 5067 Agitator Assembly 04 30 12717 Agitator Motor Bracket 05 52 3690 Control Housing Assembly 06 25 0047 01 Transformer 07 52 1773 02 EIBC Probe Assembly 08 52 3485 Con...

Page 23: ...23 Wiring Diagram 115 Volt...

Page 24: ...Plumbing Diagram Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: