Section 11 - Flame Adjustment
The combustion air baffle is NOT factory set!
Flame Adjustment
1.
Start the heater, let it run for at least 15 minutes to reach operating temperature before
proceeding.
2.
Check the chimney draft, set the barometric damper to -0.05 WC when hot and
running.
3.
Check the atomizing air pressure, set the air filter/regulator on the heater:
XT-150/200 = 12-15 PSI
XT-250/300 = 15-18 PSI
4.
Ensure that the initial fuel pressure is set according to the table in Section 10 - Burner
Startup Procedure.
5.
When using the bypass regulator, adjust the thumb screw on the fuel bypass regulator.
Lock into position. The flame should extend no more than 3/4 of the way into the
chamber.
NOTE:
Mechanical equipment like gauges and
regulators are not always 100 percent accurate,
VISUAL INSPECTION OF THE FLAME IS REQUIRED