Section 8 - Electrical Connections
Fuel Supply Pump Electrical Installation
1.
All wiring must comply with the National Electrical Code, State and Local Ordinances,
and be wired by a qualified electrician.
2.
The electrical conductors to the fuel pump motor MUST be stranded 14 GA minimum.
3.
The electrical service connections for the fuel pump motor are made in the electrical
junction box on the side of the heater.
4.
The pump motor MUST have a safety equipment ground from the main electrical serv-
ice, stranded 14 GA minimum.
5.
The electrical conductors from the electrical junction box to the pump motor must be
within approved conduit.
6.
Keep all electrical conductors and conduit away from the chimney connector as well as
any other hot surfaces. Refer to Wiring Diagram for color code, etc. Wire power to L1
and L2 on the pump. Keep the Power off until the heater is ready to be started.
Room Thermostat Installation
1.
All wiring must comply with the National Electrical Code, State and Local Ordinances,
and be wired by a qualified electrician.
2.
Install the room thermostat in accordance with the directions furnished with the
thermostat.
3.
Use
two
conductor
thermostat
wire
(24
AWG
minimum)
for
the
connection
of
the
thermostat to the T1-T2 terminals of the oil primary control that is mounted on top of the
burner.
4.
Mount the thermostat 5 feet above the floor on an inside wall away from the heater’s
warm air path.
5.
The electrical current for thermostat is 24 V, and is provided by the oil primary control.
6.
Keep the thermostat wire away from the chimney connector, or any other hot surfaces.
Refer to Section 2 for a typical thermostat installation.
WARNING: HAZARD OF ELECTRICAL SHOCK!