Section 13 - Troubleshooting
Symptom
Possible Cause
Corrective Action
C. Burner fires but then
trips primary control
1. Contaminated fuel supply
(water/antifreeze/gear lube),
dirty fuel filter
1. Drain and clean fuel-supply
tank; clean fuel filter
2.
Improper draft
2. Ensure chimney is installed
properly and draft is set
3. Clogged heat exchanger or
chimney
3. Clean heater, including upper
manifold and chimney
4. Incorrect air pressure
4. Adjust flame settings (Section
11)
5. Incorrect fuel pressure
5. Check fuel supply (Section 6)
and flame adjustment (Sec-
tion 11)
6. Improper combustion air baf-
fle setting/combustion blower
is defective
6. Adjust flame (Section 11); test
combustion blower motor,
replace if necessary
7. Oil primary control/flame
sensor defective, flame sensor
and/or turbulator improperly
adjusted/dirty
7. Clean/test/adjust compo-
nents; replace if necessary
8. Clogged nozzle and/or pre-
heater assembly
8. Clean/replace nozzle and/or
preheater assembly
D. Preheater assembly
not working
1. Cartridge heater(s) defective/
disconnected
1. Test cartridge heater(s) using
an Ohm meter:
Air heater = 112 Ω ±10%
Oil heater = 37 Ω ±10%
2. Snap disc defective
2. Test snap disc for continuty
when preheater is cold