8
Figure 22
Figure 23
Figure 21
CautIon
FoLLoW ManuFaCturer’S InStruCtIonS
on HoW to InStaLL tHe BaroMetrIC
reGuLator.
Use approximate 45 degree adj. elbows for angled
connections – NO HORIZONTAL PIPING.
InStaLLatIon
Barometric Draft Control field 6” RC/BT provided
with your model 200 Vapor Fire Unit. A draft regulator
is designed for insertion into a six (6) inch tee. Refer
to Figure 21 for mounting of the barometric damper.
It is recommended that the stove pipe be installed
with the crimped end down so that if any creosote is
formed, as a natural by-product of combustion, it will
run back towards the furnace and not run through
the joint to the outside of the smoke pipe. The sec-
tion of pipe (tee) holding the draft regulator must be
installed in either an angled or vertical direction.
The draft control can be positioned within its collar
to an upright position.
It is essential that the draft regulator be located in
the same room (pressure zone) as the furnace and
as close as possible to the flue outlet.
After installation, make certain the draft control
barometric regulator is upright and level. Tighten
the screw to hold firmly in place. See Figure 22.