LAMBRECHT meteo GmbH
Ser[LOG] Manual
Page 55 of 129
•
Standard
Linear scaling according to y=ax+b, where "a"
and "b" are calculated from the signal minimum,
signal maximum, value minimum and value
maximum.
•
PT100
Can be used for the measuring range 500Ω es-
pecially for the use of Pt100 temperature sen-
sors. In this case, a polynomial stored specifi-
cally for Pt100 sensors is used for scaling.
•
PT1000
Can be used for measuring range 5000Ω espe-
cially for the use of Pt1000 temperature sensors.
In this case, a polynomial stored specifically for
Pt1000 sensors is used for scaling.
•
Polynom
Allows the use of a 5th-order polynomial for scal-
ing the selected measuring range.
•
Look_Up_Table_1
Scaling with the use of up to 15 calibration points
in table 1.
See also chapter 5.3.6.4 Configuration of sen-
sors with look-up table
•
Look_Up_Table_2
Scaling with the use of up to 15 calibration points
in table 2.
See also chapter 5.3.6.4 Configuration of sen-
sors with look-up table
Example: Sensor type “Polynom”
Summary of Contents for Ser[LOG]
Page 9: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 9 of 129 21 Technical data 127 22 Disposal 129...
Page 68: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 68 of 129 This choice leads to the following graph...
Page 92: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 92 of 129 12 Managing the safety settings...
Page 101: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 101 of 129...
Page 102: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 102 of 129...
Page 103: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 103 of 129...
Page 104: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 104 of 129...
Page 105: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 105 of 129...
Page 106: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 106 of 129...
Page 107: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 107 of 129...