LAMBRECHT meteo GmbH
Ser[LOG] Manual
Page 41 of 129
Note: If the connected sensors are supplied via the "SENSOR SUPPLY" terminals, then all sensors
together must not consume more than 500mA. A higher current consumption puts too much strain on
the Ser[LOG]-Bus and can lead to damage!
5.3
Configuration of the Ser[LOG]
Ser[LOG] and Ser[LOG]Plus are put into operation, configured, and tested with the configuration tool
"Ser[LOG]-Commander".
Ser[LOG]_Commander is a 32 bit Windows application that can be used under the operating systems
Windows XP to Windows 10. The application can be used from a USB memory stick. Installation on the
PC is not necessary.
If you want to copy the Ser[LOG]-Commander to a USB stick or a PC, all files contained in the
PRG_SERLOG folder must be copied as well. The files must always be in the same shared directory.
5.3.1
Basic Station Configuration
Start the Ser[LOG]-Commander by calling the "SerLog_Cmd. exe".
Press the button "Configure Logger" to open the Ser[LOG] configuration window.
The available serial interfaces are deactivated at delivery, therefore the Ser[LOG] can only be reached
via:
•
Mini-USB service interface or
•
USB Bluetooth stick (CSR chipset required)
Both interfaces operate independently of the set baud rate.
5.3.1.1
Configuration via Mini-USB Service Interface
Connect the Ser[LOG] to the PC via the supplied USB-to-Mini USB cable. The Ser[LOG] is not pow-
ered via the USB interface. If it is not already done, connect the Ser[LOG] to a suitable power supply
(10... 30 VDC).
The driver software for the USB service interface is part of the Windows operating system. Under a
freshly installed Windows 10 the interface is recognized as "USB serial device". Windows driver up-
dates can load a "driver" from the company "ELMO" and the interface is then called "ELMO GMAS".
To uniquely identify the USB interface as Lambrecht service port, please update the driver for this in-
terface via the device manager by "updating" the driver. Depending on your operating system please
load the 32- or the 64-bit version from the directory
Ser[LOG]_Cmd\Ser[LOG]_SYNMET_USB_Driver
After this update the interface is recognized as "LAMBRECHT Service Port".
Summary of Contents for Ser[LOG]
Page 9: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 9 of 129 21 Technical data 127 22 Disposal 129...
Page 68: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 68 of 129 This choice leads to the following graph...
Page 92: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 92 of 129 12 Managing the safety settings...
Page 101: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 101 of 129...
Page 102: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 102 of 129...
Page 103: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 103 of 129...
Page 104: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 104 of 129...
Page 105: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 105 of 129...
Page 106: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 106 of 129...
Page 107: ...LAMBRECHT meteo GmbH Ser LOG Manual Page 107 of 129...