64
Draining Procedure
NOTE
Risk of Damage to the pump
When the coolant level in the coolant tank is too low and if it runs the pump dry, the pump can
be damaged or destroyed.
Avoid running the pump dry to prevent damage
Requirements
Unit prepared for maintenance. Refer to
Preparing the Unit for Maintenance
Coolant hoses disconnected from the unit. Refer to
Coolant cooled down to the ambient temperature.
Required Tools and Materials
Collection container/Hose – Note, unit holds approximately 5-9 liters of fluid.
Procedure
1. Make sure Drain Valve is closed.
2. Connect hose/Place collector container under the drain valve.
3. Open Drain Valve. (Position shown in Fig.)
4. Close Drain Valve once drained completely.
The coolant is now drained.
Figure 51 Draining the Coolant