35
and they should never be used with deionization (DI) filter. Furthermore, the inhibitors will be removed
from the coolant that would normally prevent corrosion.
Suggested Contaminant Limits:
PPM
Organics
Algae, Bacteria, etc.
0
Inorganic Chemicals
Calcium
<10
Chloride
<25
Copper
<1.0
Iron
<0.2
Lead
0
Magnesium
<5
Manganese
<0.05
Nitrates \ Nitrites
<10
Potassium
<2
Silicate
<5
Sodium
<4
Sulfate
<25
Hardness
<1
Total Dissolved Solids
<25
Other Parameters
pH
6.8. 7.5
Resistivity
<
3 MΩ
-cm
Requirements
Unit prepared for maintenance. Refer to
Preparing the Unit for Maintenance
Power connected to unit.
Coolant hoses connected to the unit (Make sure the hoses are corrected to the correct ports).
Required Tools and Materials
Filling funnel
Measuring cup
Absorbent cloth
Procedure
1.
Remove the Fill Cap.
2.
For information regarding coolant to be used and quantity, refer to
Use a
filling funnel to avoid moistening any current-carrying components with coolant.
Note: If refilling coolant, go to last step.
3.
Add coolant up to required level. Ideal coolant level is just below the ‘HIGH’ marking on the
front view port of the tank.
4.
Press the ‘PUMP’ button on the LCD panel to fill the coolant lines to the application.
5.
When the tank level starts reducing, continue adding coolant through the fill port, until the
ideal coolant level is reached with the pump continuously running.
6.
Note: Do not let the pump run dry as it can be damaged.
7.
Mount the coolant cap again.
The coolant is now added.
*
3 MΩ
-cm deionized water is acceptable for use the High Purity Plumbing option. Otherwise, the
maximum water resistivity should be 0.1 MΩ
-cm.
Summary of Contents for Nextreme NRC1200 Series
Page 1: ...Nextreme Recirculating Chiller Specification and User Manual Part Number 387004848 ...
Page 17: ...17 Component Locations Figure 2 Isometric Views of Unit Figure 3 Top View ...
Page 18: ...18 Figure 4 Front View Figure 5 Rear View Figure 6 Side View ...
Page 39: ...39 Figure 25 Sensor Wiring Low Voltage ...
Page 40: ...40 Plumbing Refrigeration Diagram Figure 26 Plumbing and Refrigeration Diagram ...
Page 43: ...43 Figure 31 Pump Performance of NRC5000 with Cooling Fluids Water and 40 EG W ...
Page 60: ...60 PCFLT Returns FLT fault or NO FAULTS FOUND PCFLT C Clears Fault Returns FLT Faults Cleared ...
Page 69: ...69 Declaration of Conformity ...