Vertical Convection Heaters
Owner’s Manual • Workman & Norseman
11
8. Check all connections for gas leaks using ap-
proved gas leak detectors. Gas leak testing is
performed as follows:
-- Check all pipe connections, hose connections,
fi
ttings and adapters upstream of the gas control
with approved gas leak detectors.
-- In the event a gas leak is detected, check the
components involved for cleanliness and proper
application of pipe compound before further
tightening.
-- Further tighten the gas connections as necessary
to stop the leak.
-- After all connections are checked and any leaks
are stopped, turn on the main burner.
-- Stand clear while the main burner ignites to
prevent injury caused from hidden leaks that could
cause
fl
ashback.
-- With the main burner in operation, check all
connections, hose connections,
fi
ttings and joints
as well as the gas control valve inlet and outlet
connections with approved gas leak detectors.
-- If a leak is detected, check the components
involved for cleanliness in the thread areas and
proper application of pipe compound before
further tightening.
-- Tighten the gas connection as necessary to stop
the leak.
-- If necessary, replace the parts or components
involved if the leak cannot be stopped.
-- Ensure all gas leaks have been identi
fi
ed and
repaired before proceeding.
9. A quali
fi
ed service agency must inspect the
heater before each use and at least annually.
10. Light according to instructions on heater or
within owner’s manual.
11. Make sure the heater has the proper gas regu-
lator for the application. A regulator must be
connected to the gas supply so that gas pres-
sure at the inlet to the gas valve is regulated
within the range speci
fi
ed on the dataplate at
all times. Contact your gas supplier, or the L.B.
White Co., Inc. if you have any questions.
12. This heater is con
fi
gured for use with propane
vapor withdrawal only. Consult the heater’s dat-
aplate for the gas con
fi
guration of the speci
fi
c
heater. Do not use the heater in an propane
liquid withdrawal system or application. If you
are in doubt, contact the L.B. White Co., Inc.
13. Take time to understand how to operate and
maintain the heater by using this Owner’s
Manual. Make sure you know how to shut off
the gas supply to the building and also to the
individual heater. Contact your fuel gas supplier
if you have any questions.
14. Any defects found in performing any of the
service or maintenance procedures must
be eliminated and defective parts replaced
immediately. The heater must be retested by
properly quali
fi
ed service personnel before
placing the heater back into use.
15. For indoor use only. Adequate ventilation shall
be provided in accordance with OSHA 29 CFR
1926.154, Safety Requirements for Temporary
and Portable Space Heating Devices and
Equipment, ANSI A10.10, National Fuel Gas
Code, ANSI Z223.1/NFPA54, Liqui
fi
ed Petro-
leum Gas Code, NFPA 58 or the Natural gas
and Propane Installation Code, CAN B149.1,
as appropriate.
WARNING
Fire and Explosion Hazard
■
Do not use open
fl
ame (matches, torches,
candles, etc.) in checking for gas leaks.
■
Use only approved leak detectors.
■
Failure to follow this warning can lead to
fi
res
or explosions.
■
Fires or explosions can lead to property dam-
age, personal injury or loss of life.
Summary of Contents for 320
Page 32: ...Vertical Convection Heaters www lbwhite com Owner s Manual Workman Norseman 32...
Page 65: ...Calefactores de convecci n verticales www lbwhite com Manual del usuario Workman y Norseman 32...
Page 98: ...Fournaises verticales convection www lbwhite com Manuel du propri taire Workman et Norseman 32...