V3.3 11.07.2007 KRC-AD-KRC2ed05-BA en
5. Planning
Signal
Pin
Description
Comments
+24 V internal
0 V internal
106
107
ESC power supply max. 2 A
24 V external
0 V external
88
89
In the absence of an external
power supply, 24 V / 0 V must
be jumpered internally.
An external power supply is
recommended for interlinked
systems.
+24 V
0 V
36
18
24 V control voltage for supply
to external devices, max. 4 A.
Optional
+24 V
0 V
90
72
24 V control voltage for supply
to external devices, max. 6 A.
Optional
Test output A
(test signal)
1
5
7
38
41
Makes the pulsed voltage avail-
able for the individual interface
inputs of channel A.
Connection example: enabling
switch is connected under
channel A to pin 1 (TA_A) and
pin 6.
Test output B
(test signal)
19
23
25
39
43
Makes the pulsed voltage avail-
able for the individual interface
inputs of channel B.
Connection example: safety
gate locking mechanism is con-
nected under channel B to pin
19 (TA_B) and pin 26.
Local E-STOP
channel A
20 / 21
Output, floating contacts from
internal E-STOP, max. 24 V,
600 mA
In the non-activated state, the
contacts are closed.
Local E-STOP
channel B
2 / 3
External E-STOP
channel A
4
E-STOP, dual-channel input,
max. 24 V, 10 mA.
External E-STOP
channel B
22
Enabling chan-
nel A
6
For connection of an external
dual-channel enabling switch
with floating contacts max.
24 V, 10 mA
If no enabling switch is con-
nected, pins 5 and 6 and pins
23 and 24 must be jumpered.
Only effective in TEST mode.
Enabling chan-
nel B
24
Safeguard chan-
nel A
8
For dual-channel connection of
a safety gate locking mecha-
nism, max. 24 V, 10 mA
Only effective in AUTOMATIC
mode.
Safeguard chan-
nel B
26
Drives OFF
external, channel
A (single-chan-
nel)
42
A floating contact (break con-
tact) can be connected to this
input. If the contact opens, the
drives are switched off, max.
24 V, 10 mA.
If this input is not used, pins 41/
42 must be jumpered.
Drives ON exter-
nal, channel B
(single-channel)
44
For connection of a floating
contact.
Pulse > 200 ms switches the
drives on. Signal must not be
permanently active.
Drives ON chan-
nel B
29 / 30
Floating contacts (max. 7.5 A)
signal “Drives ON”.
These contacts are only availa-
ble if a CI3 Extended or CI3
Tech board is used.
Is closed if the “Drives ON”
contactor is energized.
Summary of Contents for KR C2 edition05
Page 8: ...8 157 V3 3 11 07 2007 KRC AD KRC2ed05 BA en KR C2 edition05...
Page 72: ...72 157 V3 3 11 07 2007 KRC AD KRC2ed05 BA en KR C2 edition05 Connector pin allocation...
Page 76: ...76 157 V3 3 11 07 2007 KRC AD KRC2ed05 BA en KR C2 edition05...
Page 84: ...84 157 V3 3 11 07 2007 KRC AD KRC2ed05 BA en KR C2 edition05...
Page 157: ...157 157 V3 3 11 07 2007 KRC AD KRC2ed05 BA en...