Hardware
38 of 70
Hardware R2.2.8 11.98.02 en
Safety circuit channels
1 and 2
11 / 12
29 / 30
Floating contacts of the safety cir-
cuit
Is closed if the safeguard input is
closed during automatic operation
or if the safety switch is pressed in
the Test mode.
Test and Automatic
mode groups
48 / 46
48 / 47
Floating contacts of the operating
mode relays.
Test contact is closed if Test1 or
Test2 is selected on the KCP.
Automatic contact is closed if
Automatic or External is selected.
Rapid gauging
channels 1 to 4
13 / 14
/ 31 /
32 / 49
Inputs are read by the DSEAT at
the 125
←
s clock rate.
When a 0/1 or 1/0 edge is
detected, the actual axis values
are stored by the software.
All two--channel inputs must be set with a simultaneity of
10 ms. If this time
is longer, a contact fault or open circuit will be detected and the relays inter-
locked. The interlock is cancelled again after both channels have been re-
set.
Emergency Stop circuit, safeguard and ext. safety switch are signals that
serve safety purposes and must be used in accordance with DIN EN
60204--1 and EN 775.
Summary of Contents for KR C1
Page 1: ...Hardware R2 2 8 11 98 02 en 1 of 70 SOFTWARE KR C1 Hardware Release 2 2...
Page 30: ...Hardware 30 of 70 Hardware R2 2 8 11 98 02 en Fig 13 Circuit diagram X931 X604...
Page 32: ...Hardware 32 of 70 Hardware R2 2 8 11 98 02 en Fig 15 Inputs...
Page 34: ...Hardware 34 of 70 Hardware R2 2 8 11 98 02 en...
Page 35: ...35 of 70 Hardware R2 2 8 11 98 02 en...