BCU 560, BCU 565 · Edition 02.16
98
Parameters
11 .9 Behaviour during start-up
11 .9 .1 Minimum pause time t
BP
Parameter 62
A minimum pause time t
BP
(0 to 3600 s) can be defined to
achieve stable operation of the burners. If the post-ventilation
time set using parameter 39 has elapsed and no signal (
ϑ
) is
received at terminal 1 (burner shut down), a restart and cooling
are prevented for the duration of the minimum pause time t
BP
.
If a signal is applied to terminal 1 (burner start-up) or terminal 2
(cooling) during the minimum pause time, status display Delay
H0
will appear.