BCU 560, BCU 565 · Edition 02.16
125
18 Maintenance
The fail-safe outputs (valve outputs V1, V2 and V3) of the power
module are monitored for correct functioning. In the event of
a fault, the system is set to a safe status using a second shut-
down method (isolation of the valve outputs from the mains).
In the event of a defect (e.g. fault 36), the power module must
be replaced.
See www.partdetective.de
for a replacement/order option for the power module.
The device and user statistics can be displayed using the
operator-control unit OCU or engineering tool BCSoft for fur-
ther diagnostics and troubleshooting. The user statistics can
be reset using engineering tool BCSoft.