BCU 560, BCU 565 · Edition 02.16
46
Profinet > GSD file for PLC configuration > Modules for cyclic data exchange
“Remaining times ” module (device
➔
controller) – slot 6
This module transfers the remaining times of various processes
from the BCU to the PLC. The remaining time occupies 2 bytes.
Bit Byte n
Byte n+1 Data type
Format
Value
0
Remaining times
Word
DEC
0 – 6554
(0 – 6554 s)
1
2
3
4
5
6
7
“Remaining times of the valve proving system” module
(device
➔
controller) – slot 7
Only for BCU..C1.
The module in BCU..C0 contains no information.
This module transfers the remaining time of the valve prov-
ing system from the BCU..C1 to the PLC. The remaining time
occupies 2 bytes.
The valve check runs parallel to other time-related processes,
e.g. pre-purge. To display the remaining time of the valve
proving system separately, it is transferred separately.
Bit Byte n
Byte n+1 Data type
Format
Value
0
Remaining times
of the valve prov-
ing system
Word
DEC
0 – 6554
(0 – 6554 s)
1
2
3
4
5
6
7
▼