Parameters > Functions of terminals 50, 51, 65, 66, 67 and 68
11 .11 .5 Function of terminal 67
Parameter 72
Parameter 72 = 0: Off
Parameter 72 = 8: AND with input at terminal 46 (emergency
stop)
Parameter 72 = 9: AND with input at terminal 47 (air
min.
pres-
sure switch)
Parameter 72 = 10: AND with input at terminal 48 (air flow
pressure switch)
Parameter 72 = 21: Multi-flame control (MFC) start-up condi-
tions
1
2
34
6
45
65
66
67
68
49
50
51
17
18
37
38
13
14
15
5 6
9
11 12
10
BCU 56x
7
3,15AT
µC
88
c
c
62 61
41
42
24V
DC
44
53
54
0,6 × I
N
IFW
IFW
L1