BCU 560, BCU 565 · Edition 02.16
95
Parameters
11 .7 menox
®
11 .7 .1 menox pre-ventilation time t
VLM
Parameter 28
This parameter is used to define the time during which the air
valve is open in menox
®
mode before the normal start-up.
Suitable for burners starting with full air capacity.
The possible settings are from 0 to 10 s in 0.1 s steps, from 10
to 250 s in 1 s steps.
t
SA1
t
Z
A2
A4
00
t
t
VLM
A1
2
10
47
A
88
ϑ
46
1
11
9
5
37-38
13
V1
14
V2
17-18
PZL
After the start-up signal (
ϑ
) has been applied and the “no
flow” state check has been conducted successfully, the air
valve is opened. Start-up of the burner commences with no
interruption of the air supply after expiry of the programmable
pre-ventilation time t
VLM
.
Parameter setting for this example sequence:
P06 = 5; P16 = 0, see also page 74 (Air pressure cut-out
delay). The gas valve does not open until the pressure switch
has switched.
If the menox
®
pre-ventilation time t
VLM
(P28) > the running
time (P42) and there is no signal from the pressure switch
at terminal 47 after expiry of the running time (P42), the BCU
performs a shut-down depending on parameter 15 (Low air
pressure protection).
11 .7 .2 Switchover to menox
®
operating mode
Parameter 64
As soon as there is a signal at the menox
®
input (terminal 44),
the BCU can switch to flame or menox
®
mode immediately
or upon the next burner start.
Switchover from flame mode to menox
®
mode
Parameter 64 = 0: on next burner start. As long as the start-up
signal is present, the burner control unit will remain in flame
mode. The switchover to menox
®
mode does not take place
until the next burner start.
Parameter 64 = 1: immediately. The switchover to menox
®
mode takes place immediately. The start-up signal must be
applied to terminal 1. The burner in flame mode is switched
off and restarted in menox
®
mode.
Switchover from menox
®
mode to flame mode
Parameter 64 = 0: on next burner start. As long as the start-
up signal is present, the burner control unit will remain in
menox
®
mode. The switchover to flame mode does not take
place until the next burner start.
Parameter 64 = 1: immediately. The switchover to flame mode
takes place immediately. The start-up signal must be applied
to terminal 1. The burner in menox
®
mode is switched off and
restarted in flame mode.