7.30830.32.00
45
Press
↵
key to return to Fct. 1.07 – 1.10, status outputs A1, A2, D1 or D2.
External range change by control input
Fct. 1.11 or 1.12 Control inputs C1 or C2
Press
→
key
Press
↑
key as often as required to set one of the control inputs C1 or C2 to range change “EXT. RNG.”.
Press
↵
key to change to numerical setting, 1st number (cursor) flashes.
Change flashing number (cursor) with keys
↑
and
↓
. Use
←
and
→
keys to shift cursor 1 place to left or to right.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Setting range:
5 – 80 PERCENT of Q
100%
(=low to high range ratio 1:20 to 1:1.25)
Press
↵