Commissioning/configuration
© 2022 KOSTAL Solar Electric GmbH
67
6.5 Settings for bank 2
The following settings can be configured via bank 2:
Configurable functions:
Bank
DIP switch
Function
2
1-3
Max. charging current per phase
4-5
No function (default setting OFF)
6-8
Maximum current for house connection
Setting maximum charging current per phase
The max. charging current per phase for charging an electric vehicle can be set between
6-16 A. This must be compliant with the fuse protection (line circuit breaker / residual cur-
rent device) of the wallbox.
Configure the setting as desired.
Bank 2
Bank 1
1
2
4
5
3
6
7
8
ON
1
2
4
5
3
6
7
8
ON
2 1
3
16 A
13 A
10 A
6 A
ON
OFF
Bank 2
1
2
4
5
3
6
7
8
ON
1ph / 3ph
16 A = 3,7 / 11 kW
13 A = 3,0 / 9,0 kW
10 A = 2,3 / 6,9 kW
6 A = 1,4 / 4,1 kW
Typ 2
Wallbox
Configurable functions:
Bank
DIP switch
Charging current
per phase (A)
Charging power (kW)
3
2
1
Connection
1-phase
3-phase
2
OFF
OFF
OFF
16
3.7
11
ON
OFF
OFF
13
3.0
9
ON
OFF
ON
10
2.3
6.9