Connection of additional components
© 2022 KOSTAL Solar Electric GmbH
54
5.3 Connection of optional shunt releases
In some countries, automatic AC shutdown is required in the event of a fault. A shunt re-
lease can be connected to the wallbox for this purpose.
Connecting the shunt release
1.
Install shunt release in the house connection box. Follow the manufacturer's installa-
tion instructions.
2.
Route the cable between the wallbox and shunt release.
DANGER
Risk of death due to electrical shock and discharge!
If the cable is not kept reliably separate from active electrical equipment, touchable parts
may be live. As a result, people may be seriously injured or killed by electric shock.
When routing and connecting the cable, keep it reliably separate from active electrical
equipment.
3.
Use a suitable to tool to cut the required cable inlet out of the wallbox. Cable inlets are
located on the rear, bottom and top.
4.
Insert the appropriate membrane cable entry (included in the scope of delivery) into
the respective cable inlet.
For cable inlet on the top or bottom:
Use membrane cable entries with strain relief.
For cable inlet on the rear:
Use membrane cable entries without strain relief.
5.
Insert the cables into the wallbox. To do this, a hole must be pierced in the mem-
brane.
NOTE
To prevent rainwater from entering, the hole in the membrane should not be any larger
than the cables.
6.
Strip the cable.
7.
Strip 10 mm of insulation from the wires.