Installation
© 2022 KOSTAL Solar Electric GmbH
46
2.
Insert the appropriate membrane cable entry (included in the scope of delivery) into
the respective cable inlet.
For cable inlet on the top or bottom:
Use membrane cable entries with strain relief.
For cable inlet on the rear:
Use membrane cable entries without strain relief.
3.
Insert the cables into the wallbox. To do this, a hole must be pierced in the mem-
brane.
POSSIBLE DAMAGE
Damage to the device due to rainwater ingress
To prevent rainwater from entering, the hole in the membrane should not be any larger
than the cables. The electronic components may experience subsequent damage.
✔
Cable routing complete.
Mounting wallbox
The supplied fastening material (screws, screw anchors) is only suitable for mounting on
concrete, brick and wooden walls.
4 x 5x60 TX20
≈1500
1.
Screw the wallbox to the wall using screw anchors and screws. Follow the mounting
instructions on the wallbox drilling template.